Component List Editor 8.7 How to configure the "Loop in Alarm" function Procedure 1. Start´the "Alarm Logging" editor. You can select the "Loop in Alarm" function from the "Tag/Action" tab or from the "Loop in Alarm" column in the message "Properties" dialog box. The WinCC default here is "Open Picture". 2. In the "Picture name/Call parameter" input box, enter the measuring point name, e.g. "FIC_752_003". Go to the "Split Screen Manager" in the Function Browser to select the "LoopInAlarm" function. Click "OK". "OpenPicture" is replaced by "LoopInAlarm". Caution: Do not double-click "LoopInAlarm"! If this occurs accidentally, then click "Cancel". The additional "Parameter Assignment" dialog box will close. Note The standard function "Open Picture" may not be used in the PCS 7 environment. A picture opened with this function overlays the standard runtime environment. Now, operator input is no longer possible. WinCC/Options for Process Control System Manual, 02/2013, A5E32315704-AA 281