Power Switching Devices
Comparison Guide
Initial
Cost
3 Year
Control
Cost ① Life
Heater
EMI
Response
Life GenerationControl RateOptions
Comments
Low for low Highest
current
Electromechanical Relay and Contactor
Limited
Shortest
Yes, coil
Poor
Slowest
None
electrical and and contacts
mechanical
To extend life the cycle
time is normally extended
to 30 seconds or more.
Hybrid Power Switch
Low
Medium
High
Good
Minimal
Good
Fast
None
Such as Watlow E-SAFE II
and NO ARC relays.
Mercury Displacement Relay (MDR)
Low for
Medium
High
Good
Yes, coil
Fair to
Medium
None
Mercury is not desirable.
low to
and contact
good
to fast
Minimum cycle time is
medium two seconds. Position
currentsensitive.
Solid State Relay (SSR) Fixed Time Base
Medium
Extended
Extended
Minimal
Good
Fast
None
Excellent control with one
Medium
second cycle time.
Requires heatsink.
Silicon Controlled Rectifier (SCR) Fixed Time Base
Medium
Low
Extended
Extended
Minimal
Good
Fast
None
Excellent control with one
second cycle time.
SCR Burst Firing
High
Low
Extended
Longest
Minimal
Excellent Fastest
None
Fastest variable time base
unit.
SCR Phase-Angle Firing
High
Low
Extended
Longest
High
Excellent Fastest
Current
Required for tungsten
limit
elements, transformers,
or for current limiting.
Saturable Core Reactor
Highest
Low
Extended
Longest
Minimal
Very
Fast
Current
Cannot be turned full on
good
limit
or off, inefficient.
①Includes heater replacement and lost production.
306
WATLOW®