CHAPTER 3 INSTALLATION AND STARTUP 3.4 Startup The end of the 10BASE-5 cable should be connected by end resistance. If there is no end resistance, there may be an error in communication. After connecting the communication cable, apply the power and check if the LED is active normally. If normal, download the relevant program by GMWIN/KGLWIN to the PLC and execute the program. 3.4.1 Notices for the system configuration 1) IP addresses should be different from each other including this module. If the same addresses are connected, a communication error may occur leading to communication problems. The HS_Link station no. of all stations will also be different from each other in order to use the HS_Link service. 2) Use the communication cable as specified. If not, a serious error may occur to communications. 3) Check the communication cable if disconnected or shorted prior to installation. 4) Tighten the communication cable connector until firmly connected. If the cable connection is unstable, a serious error may occur to communications. 5) If a remote communication cable is connected, keep the cable far away from the power line or conductible noise. 6) Since the copper cable is not flexible, it is to be diverged a minimum of 30cm away from the connector in the communication module. If the cable is bent at a right angle, this may cause cable disconnection or connector damage to the communication module. 7) If LED operation is abnormal, refer to Chapter 14 Troubleshooting to determine the cause and actions to solve the problem. Contact the service center if the error occurs again. 3-9