Download User`s Manual
Transcript
6. Terminal Wiring Diagrams NOTE Do not use unassigned terminals as relay terminals. ■ UT750 Single-loop Control (Model UT750-0䊐 or UT750-5䊐) ■ UT750 Single-loop Position Proportional Control (Model UT750-1䊐) Communication 1 Communication 2 (PSL1) (PSL2) RS-485 communication Communication 1 Communication 2 (PSL1) (PSL2) High performance * Wiring can only be carried out RS-485 communication for controllers with communication functions. 23 24 28 RSB(+) SDB(+) 29 SDA(-) 30 25 RDB(+) 26 Remote input TC input RSA(-) SG 22 - 12 b NC 1 NO 2 Note: Select this option from the OT1 parameter. * Time proportional PID relay contact output is configured at factory before shipment. 3 COM CAUTION Power supply 41 31 21 11 2 42 32 22 12 12 + 13 - Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock. 3 43 33 23 13 4 44 34 24 14 5 45 35 25 15 6 46 36 26 16 Retransmission output 1* Control output 47 37 27 17 8 48 38 28 18 9 9 49 39 29 19 16 + 10 10 50 40 30 20 17 - 8 N Note: Select this option from the OT1 parameter. * Retransmission output 2 is available only when “relay” is selected as the type of control output. Current/voltage pulse output 7 L Retransmission output 2* 0-20mADC, 4-20mADC Voltage pulse (12 V) 17 - DO3 4 Common COM 7 DO4 34 Alarm 3 output (Note 1) DO5 33 Alarm 4 output (Note 2) DO6 32 No function DO7 31 Common COM 35 50 * Retransmission output 1 is not available if a 15 V DC loop power supply is used. 12 + 250 Ω 4-20mA 13 21 + SG 13 - 13 B Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC. mV/V input Default: 1-5 V DC Note: Connecting a 250 Ω resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs) 12 + 13 - NOTE Installation category (overvoltage category): II (IEC1010-1) 100% N CAUTION 8 9 1 41 31 21 11 2 42 32 22 12 3 43 33 23 13 14 + 4 44 34 24 14 15 - 5 45 35 25 15 6 46 36 26 16 7 47 37 27 17 8 48 38 28 18 9 49 39 29 19 10 50 40 30 20 Retransmission output 1* 45 Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock. 10 14.5-18.0 V DC (21 mA DC max.) 11 A 47 Retransmission output 2 4-20 or 0-20 mA DC Default: 4-20 mA DC 15 V DC loop power supply* Default: Unspecified retransmission type 16 + 17 - 14 + 0-20mADC, 4-20mADC 15 - * PV retransmission is configured at factory before shipment. Load resistance: 600 Ω or less * If 15 V DC loop power supply is used, retransmission output 1 cannot be used. 14.5-18.0 V DC (21 mA DC max.) Default: 4-20 mA DC Allowable range: 100-240 V AC (10%) (free voltage) 50/60 Hz shared Alarm 1 output DO1 6 Alarm 2 output DO2 5 Alarm 3 output (Note 1) DO3 4 40 Common COM 7 39 Alarm 4 output (Note 2) DO4 34 Alarm 3 output (Note 1) DO5 33 Alarm 4 output (Note 2) DO6 32 No function DO7 31 Common COM 35 Transistor contact 19 18 38 37 36 20 Contact rating: 12 V DC, 10 mA or more * The dual-loop type controller (UT750-5ⵧ) only Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA “Current output terminal ( 46 and 47 )” can be used for retransmission output 2. Load resistance: 600 Ω or less * The functions of the external contact inputs are the defaults for single-loop control. To change the functions, reconfigure the contact input registration parameters. External contact outputs (terminals 1 , 2 and 3 ) (terminals 16 and 17 ) SG * When receiving 4-20 mA DC current signals, set the PV input type to 1-5 V DC (setpoint “41”). 12 + 46 L * The functions of the external contact inputs are the defaults for single-loop control. To change the functions, reconfigure the contact input registration parameters. NOTE 27 Contact rating: 250 V AC, 3 A Resistance: 100 to 2.5 k 30 V DC, 3 A (resistance load) Load resistance: 600 Ω or less Note 1: The alarm 3 output parameters of the DO3 and DO5 outputs share the same function. Note 2: The alarm 4 output parameters of the DO4 and DO6 share the same function. (terminals 1 , 2 and 3 ) Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA COM Transistor Transistor Alarm 4 output (Note 2) 49 Relay Relay Alarm 3 output (Note 1) * The functions of the external contact outputs are the defaults for single-loop control. To change the functions, reconfigure the contact output registration setup parameters. 30 RTD input 䊏 Receiving 4-20 mA DC Current Signals with the Controller 12 b RSA(-) Feedback input 0% 48 L (Reverse) RDA(-) Power supply 15 V DC loop power supply* 15 - H (Direct) 26 Power supply 0-20mADC, 4-20mADC 14 + Relay contact output 4-20 or 0-20 mA DC Default: 4-20 mA DC 16 + * Factory-set to “PV retransmission.” External contact inputs (Note) Contact +5V When switching among target setpoints 1 to 8: UT DI1 1.SP2.SP 3.SP4.SP 5.SP6.SP7.SP 8.SP DI1 19 +5V DI1 ON OFF ON OFF ON OFF ON OFF DI2 Note: External Contact Input DI2 OFF ON ON OFF OFF ON ON OFF DI2 18 If the power is turned on when the external +5V DI3 OFF OFF OFF ON ON ON ON OFF contact input is OFF, the mode (SPNO, R/L, DI3 DI4 OFF OFF OFF OFF OFF OFF OFF ON or A/M) existing before the power is turned DI3 40 +5V off will be continued. (except for RUN/STOP) * If all of the contact inputs are set to OFF, DI4 the controller uses the immediately +5V preceding target setpoint. DI4 39 * OT1 is a setup parameter. DI5 AUTO when DI5=ON You can change the settings of the parameter OT1 to change the control output type. DI5 38 +5V MAN when DI5=OFF See Initial Settings User’s Manual . DI6 STOP when DI6=ON DI6 37 +5V Correspondence between parameter OT1 and control output types RUN when DI6=OFF DI7 OT1=0 (factory-set default) OT1=1 OT1=2 OT1=3 Remote when DI7=ON DI7 36 Local when DI7=OFF Time proportional control Time proportional control Current output On-off control COM Relay output Voltage pulse output (terminals 16 and 17 ) Relay output COM 20 Common DO2 5 Alarm 2 output 15 - Default: 4-20 mA DC UT DO1 6 Alarm 1 output 14 + Default: Unspecified retransmission type Allowable range: 100-240 V AC (10%) (free voltage) 50/60 Hz shared External contact outputs NOTE Installation category (overvoltage category): II (IEC1010-1) Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load) Power supply 1 Note: Connecting a 250 Ω resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs) * Wiring can only be carried out for controllers with remote input. 22 - Position proportional control output mV/V input Relay contact output 29 SDA(-) 25 RDB(+) 13 - 13 B SG 24 RSB(+) TC input Remote input 250 Ω 4-20mA 13 - Default: 1-5 V DC 28 23 SDB(+) 12 + 12 + Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC. High performance * Wiring can only be carried out RS-485 communication RS-485 communication for controllers with communication functions. * When receiving 4-20 mA DC current signals, set the PV input type to 1-5 V DC (setpoint “41”). RTD input 11 A 21 + RDA(-) 27 Control output 䊏 Receiving 4-20 mA DC Current Signals with the Controller PV input * Not configured at factory before shipment See Initial Settings User’s Manual . * Wiring can only be carried out for controllers with remote input. PV input * Not configured at factory before shipment See Initial Settings User’s Manual . UT * The functions of the external contact outputs are the defaults for single-loop position proportional control. To change the functions, reconfigure the contact output registration setup parameters. External contact inputs (Note) Contact +5V DI1 1.SP2.SP 3.SP4.SP 5.SP6.SP7.SP 8.SP DI1 19 +5V Note 1: The alarm 3 output parameters of the DO3 and DO5 DI1 ON OFF ON OFF ON OFF ON OFF DI2 outputs share the same function. DI2 OFF ON ON OFF OFF ON ON OFF DI2 18 +5V Note 2: The alarm 4 output parameters of the DO4 and DO6 DI3 OFF OFF OFF ON ON ON ON OFF DI3 share the same function. DI4 OFF OFF OFF OFF OFF OFF OFF ON DI3 40 +5V * If all of the contact inputs are set to OFF, DI4 the controller uses the immediately +5V preceding target setpoint. DI4 39 Note: External Contact Input DI5 AUTO when DI5=ON If the power is turned on when the external DI5 38 +5V MAN when DI5=OFF contact input is OFF, the mode (SPNO, R/L, DI6 or A/M) existing before the power is turned STOP when DI6=ON DI6 37 +5V RUN when DI6=OFF off will be continued. (except for RUN/STOP) DI7 Remote when DI7=ON DI7 36 Local when DI7=OFF COM COM 20 Common communication functions. 24 IMPORTANT The controller is factory-set to the Single-loop Control. Change the setting of the Control Output Type (OT1) parameter to the Heating/Cooling Control. Heating-side control output SDA(-) RDA(-) 27 SG SG PV input * Not configured at factory before shipment See Initial Settings User’s Manual . Remote input 21 + 25 RDB(+) 26 30 22 - TC input RTD input NO 2 COM 3 37 36 20 1 41 31 21 11 2 42 32 22 12 PV input 0.4-2.0 V DC signal 13 Two-wire transmitter 14 12 b 250 Ω 4-20mA Loop power supply 14.518.0 V DC 4-20mADC 13 - 13 B 15 mV/V input Note: Connecting a 250 Ω resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs) 13 - Note: Connecting a 100 resistor to the terminals is optional. Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs) NOTE Installation category (overvoltage category): II (IEC1010-1) Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load) Power supply Power supply L 8 N 3 43 33 23 13 4 44 34 24 14 5 45 35 25 15 6 46 36 26 16 7 47 37 27 17 8 48 38 28 18 9 49 39 29 19 16 + 10 50 40 30 20 17 - * Factory-set to “PV retransmission.” Retransmission output 1* CAUTION Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock. 9 10 Heating-side control output External contact outputs Relay Alarm 1 output DO1 6 Alarm 2 output DO2 5 UT Cooling-side control DO4 34 output (Note) Transistor Alarm 4 output DO6 32 No function DO7 31 Common COM 35 15 - Default: Unspecified retransmission type Cooling-side control output 0-20mADC, 4-20mADC 14 + Default: 4-20 mA DC 15 * The functions of the external contact outputs are the defaults for single-loop heating/cooling control. To change the functions, reconfigure the contact output registration setup parameters. 4-20 or 0-20 mA DC 14 + 15 - 14.5-18.0 V DC (21 mA DC max.) Default: 4-20 mA DC 16 + 17 - 14 + 15 V DC loop power supply* 0-20 mA DC 4-20 mA DC, voltage pulse (12 V) * Retransmission output 1 is not available if a 15 V DC loop power supply is used. * If you define the cooling-side output as current output, retransmission output 1 and the 15 V DC loop power supply can no longer be used. * The functions of the external contact inputs are the defaults for single-loop heating/cooling control. To change the functions, reconfigure the contact input registration parameters. External contact inputs (Note) Contact +5V DI1 1.SP2.SP 3.SP4.SP 5.SP6.SP7.SP 8.SP DI1 19 +5V DI1 ON OFF ON OFF ON OFF ON OFF DI2 DI2 OFF ON ON OFF OFF ON ON OFF DI2 18 +5V DI3 OFF OFF OFF ON ON ON ON OFF DI3 DI4 OFF OFF OFF OFF OFF OFF OFF ON DI3 40 +5V * If all of the contact inputs are set to OFF, DI4 Note: External Contact Input the controller uses the immediately Relay contact rating: 240 V AC, 1 A +5V preceding target setpoint. DI4 39 If the power is turned on when the external 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA contact input is OFF, the mode (SPNO, R/L, DI5 AUTO when DI5=ON DI5 38 +5V or A/M) existing before the power is turned MAN when DI5=OFF DI6 off will be continued. (except for RUN/STOP) STOP when DI6=ON DI6 37 +5V RUN when DI6=OFF DI7 Remote when DI7=ON DI7 36 Local when DI7=OFF NOTE COM * The dual-loop type controller (UT750-5ⵧ) only COM 20 Common “Current output terminal ( 46 and 47 )” can be used for retransmission output 2. COM 7 DO5 33 Retransmission output 2* 0-20mADC, 4-20mADC Voltage pulse (12 V) Note: If you define the DO3 output as the cooling-side control output, the DO4 output serves as the alarm 4 output. Inversely, if you define the DO4 output as the cooling-side control output, the DO3 output serves as the alarm 3 output. Cooling-side control DO3 4 output (Note) Alarm 3 output Note: Select this option from the OT1 parameter. * Retransmission output 2 is available only when “relay” is selected as the type of heating-side control output. Current/voltage pulse output Allowable range: 100-240 V AC (10%) (free voltage) 50/60 Hz shared Common 38 12 + 13 - Default: 1-5 V DC Note: Select this option from the OT1 parameter. * When receiving 4-20 mA DC current signals, set the PV input type to 1-5 V DC (setpoint “41”). 11 A 12 + 1 䊏 Receiving 4-20 mA DC Current Signals with the Controller 12 + Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC. Relay contact output NC 39 12 * Wiring can only be carried out for controllers with remote input. 28 RSB(+) RSA(-) 40 External resistor 100 (Note) High performance * Wiring can only be carried out RS-485 communication for controllers with 29 18 䊏 15 V DC Power Supply Wired to Sensor in Two-wire System Configuration Communication 1 Communication 2 (PSL1) (PSL2) 23 SDB(+) 19 Contact rating: 12 V DC, 10 mA or more ■ UT750 Single-loop Heating/Cooling Control (Model UT750-0䊐 or UT750 -5䊐) RS-485 communication Transistor contact When switching among target setpoints 1 to 8: UT Transistor contact When switching among target setpoints 1 to 8: UT * OT1 is a setup parameter. You can change the settings of the parameter OT1 to change the control output type. See Initial Settings User’s Manual . 19 18 40 39 38 37 36 20 Contact rating: 12 V DC, 10 mA or more Correspondence between parameter OT1 and heating-side output types/cooling-side output types OT1=4 OT1=5 OT1=6 OT1=7 OT1=8 OT1=9 OT1=10 OT1=11 OT1=12 Heating side: Relay output (terminals 1 , 2 and 3 ) Cooling side: Relay output (terminals 4 and 7 ) Heating side: Voltage pulse output (terminals 16 and 17 ) Cooling side: Relay output (terminals 4 and 7 ) Heating side: Current output (terminals 16 and 17 ) Cooling side: Relay output (terminals 4 and 7 ) Heating side: Relay output (terminals 1 , 2 and 3 ) Cooling side: Transistor output (terminals 34 and 35 ) Heating side: Voltage pulse output (terminals 16 and 17 ) Cooling side: Transistor output (terminals 34 and 35 ) Heating side: Current output (terminals 16 and 17 ) Cooling side: Transistor output (terminals 34 and 35 ) Heating side: Relay output (terminals 1 , 2 and 3 ) Cooling side: Current output (terminals 14 and 15 ) Heating side: Voltage pulse output (terminals 16 and 17 ) Cooling side: Current output (terminals 14 and 15 ) Heating side: Current output (terminals 16 and 17 ) Cooling side: Current output (terminals 14 and 15 ) The types of control output, “relay output” and “voltage pulse output” shown in the table above refer to those of time proportional control. To change to a relay output for on-off control, select “Relay Terminals” and change the setpoint of the proportional band to “0.” IM 05D01B02-01E (2)