6. Terminal Wiring Diagrams
NOTE
Do not use unassigned terminals as relay terminals.
■ UT750 Single-loop Control (Model UT750-0䊐 or UT750-5䊐)
■ UT750 Single-loop Position Proportional Control (Model UT750-1䊐)
Communication 1 Communication 2
(PSL1)
(PSL2)
RS-485 communication
Communication 1 Communication 2
(PSL1)
(PSL2)
High performance
* Wiring can only be carried out
RS-485 communication for controllers with
communication functions.
23
24
28 RSB(+)
SDB(+)
29
SDA(-)
30
25 RDB(+)
26
Remote input
TC input
RSA(-)
SG
22 -
12 b
NC
1
NO
2
Note: Select this option from
the OT1 parameter.
* Time proportional PID relay contact
output is configured at factory
before shipment.
3
COM
CAUTION
Power supply
41
31
21
11
2
42
32
22
12
12 +
13 -
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
3
43
33
23
13
4
44
34
24
14
5
45
35
25
15
6
46
36
26
16
Retransmission output 1*
Control output
47
37
27
17
8
48
38
28
18
9
9
49
39
29
19
16 +
10
10
50
40
30
20
17 -
8
N
Note: Select this option from the OT1 parameter.
* Retransmission output 2 is available
only when “relay” is selected as the
type of control output.
Current/voltage
pulse output
7
L
Retransmission
output 2*
0-20mADC,
4-20mADC
Voltage pulse (12 V)
17 -
DO3 4
Common
COM 7
DO4 34
Alarm 3 output
(Note 1)
DO5 33
Alarm 4 output
(Note 2)
DO6 32
No function
DO7 31
Common
COM 35
50
* Retransmission output 1 is not available if a
15 V DC loop power supply is used.
12 +
250 Ω 4-20mA
13 21 +
SG
13 -
13 B
Specify in a range of
1-5 V DC, 0-2 V DC,
or 0-10 V DC.
mV/V input
Default: 1-5 V DC
Note: Connecting a 250 Ω resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
12 +
13 -
NOTE
Installation category (overvoltage category): II (IEC1010-1)
100%
N
CAUTION
8
9
1
41
31
21
11
2
42
32
22
12
3
43
33
23
13
14 +
4
44
34
24
14
15 -
5
45
35
25
15
6
46
36
26
16
7
47
37
27
17
8
48
38
28
18
9
49
39
29
19
10
50
40
30
20
Retransmission output 1*
45
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
10
14.5-18.0 V DC
(21 mA DC max.)
11 A
47
Retransmission
output 2
4-20 or
0-20 mA DC
Default: 4-20 mA DC
15 V DC loop power supply*
Default: Unspecified
retransmission type
16 +
17 -
14 +
0-20mADC,
4-20mADC
15 -
* PV retransmission is configured at factory
before shipment.
Load resistance: 600 Ω or less
* If 15 V DC loop power supply is used,
retransmission output 1 cannot be used.
14.5-18.0 V DC
(21 mA DC max.)
Default: 4-20 mA DC
Allowable range: 100-240 V AC (10%)
(free voltage)
50/60 Hz shared
Alarm 1 output
DO1 6
Alarm 2 output
DO2 5
Alarm 3 output
(Note 1)
DO3 4
40
Common
COM 7
39
Alarm 4 output
(Note 2)
DO4 34
Alarm 3 output
(Note 1)
DO5 33
Alarm 4 output
(Note 2)
DO6 32
No function
DO7 31
Common
COM 35
Transistor contact
19
18
38
37
36
20
Contact rating: 12 V DC, 10 mA or more
* The dual-loop type controller (UT750-5ⵧ) only
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Transistor contact rating: 24 V DC, 50 mA
“Current output terminal ( 46 and 47 )” can be used for retransmission output 2.
Load resistance: 600 Ω or less
* The functions of the external contact inputs are the defaults for single-loop control.
To change the functions, reconfigure the contact input registration parameters.
External contact outputs
(terminals 1 , 2 and 3 )
(terminals 16 and 17 )
SG
* When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint “41”).
12 +
46
L
* The functions of the external contact inputs are the defaults for single-loop control.
To change the functions, reconfigure the contact input registration parameters.
NOTE
27
Contact rating: 250 V AC, 3 A Resistance: 100 to 2.5 k
30 V DC, 3 A (resistance load)
Load resistance: 600 Ω or less
Note 1: The alarm 3 output parameters of the DO3 and DO5 outputs share the same
function.
Note 2: The alarm 4 output parameters of the DO4 and DO6 share the same function.
(terminals 1 , 2 and 3 )
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Transistor contact rating: 24 V DC, 50 mA
COM
Transistor
Transistor
Alarm 4 output
(Note 2)
49
Relay
Relay
Alarm 3 output
(Note 1)
* The functions of the external contact outputs are the defaults for single-loop control.
To change the functions, reconfigure the contact output registration setup parameters.
30
RTD input
䊏 Receiving 4-20 mA DC Current
Signals with the Controller
12 b
RSA(-)
Feedback input
0%
48
L
(Reverse)
RDA(-)
Power supply
15 V DC loop power supply*
15 -
H
(Direct)
26
Power supply
0-20mADC,
4-20mADC
14 +
Relay contact output
4-20 or
0-20 mA DC
Default: 4-20 mA DC
16 +
* Factory-set to “PV retransmission.”
External contact inputs (Note)
Contact +5V
When switching among target setpoints 1 to 8: UT
DI1
1.SP2.SP 3.SP4.SP 5.SP6.SP7.SP 8.SP
DI1 19
+5V
DI1 ON OFF ON OFF ON OFF ON OFF
DI2
Note: External Contact Input
DI2 OFF ON ON OFF OFF ON ON OFF
DI2 18
If the power is turned on when the external
+5V
DI3 OFF OFF OFF ON ON ON ON OFF
contact input is OFF, the mode (SPNO, R/L,
DI3
DI4 OFF OFF OFF OFF OFF OFF OFF ON
or A/M) existing before the power is turned
DI3 40
+5V
off will be continued. (except for RUN/STOP) * If all of the contact inputs are set to OFF,
DI4
the controller uses the immediately
+5V
preceding target setpoint.
DI4 39
* OT1 is a setup parameter.
DI5
AUTO when DI5=ON
You can change the settings of the parameter OT1 to change the control output type.
DI5 38
+5V
MAN when DI5=OFF
See Initial Settings User’s Manual .
DI6
STOP when DI6=ON
DI6 37
+5V
Correspondence between parameter OT1 and control output types
RUN when DI6=OFF
DI7
OT1=0 (factory-set default)
OT1=1
OT1=2
OT1=3
Remote when DI7=ON
DI7 36
Local when DI7=OFF
Time proportional control
Time proportional control
Current output
On-off control
COM
Relay output
Voltage pulse output
(terminals 16 and 17 )
Relay output
COM 20
Common
DO2 5
Alarm 2 output
15 -
Default: 4-20 mA DC
UT
DO1 6
Alarm 1 output
14 +
Default: Unspecified
retransmission type
Allowable range: 100-240 V AC (10%)
(free voltage)
50/60 Hz shared
External contact outputs
NOTE
Installation category (overvoltage category): II (IEC1010-1)
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Power supply
1
Note: Connecting a 250 Ω resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
* Wiring can only be carried out for
controllers with remote input.
22 -
Position proportional control output
mV/V input
Relay contact output
29
SDA(-)
25 RDB(+)
13 -
13 B
SG
24
RSB(+)
TC input
Remote input
250 Ω 4-20mA
13 -
Default: 1-5 V DC
28
23 SDB(+)
12 +
12 +
Specify in a range of
1-5 V DC, 0-2 V DC,
or 0-10 V DC.
High performance
* Wiring can only be carried out RS-485 communication RS-485 communication
for controllers with
communication functions.
* When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint “41”).
RTD input
11 A
21 +
RDA(-)
27
Control output
䊏 Receiving 4-20 mA DC Current
Signals with the Controller
PV input * Not configured at factory before shipment
See Initial Settings User’s Manual .
* Wiring can only be carried out for
controllers with remote input.
PV input * Not configured at factory before shipment
See Initial Settings User’s Manual .
UT
* The functions of the external contact outputs are the defaults for
single-loop position proportional control. To change the functions,
reconfigure the contact output registration setup parameters.
External contact inputs (Note)
Contact +5V
DI1
1.SP2.SP 3.SP4.SP 5.SP6.SP7.SP 8.SP
DI1 19
+5V
Note 1: The alarm 3 output parameters of the DO3 and DO5
DI1 ON OFF ON OFF ON OFF ON OFF
DI2
outputs share the same function.
DI2 OFF ON ON OFF OFF ON ON OFF
DI2 18
+5V
Note 2: The alarm 4 output parameters of the DO4 and DO6
DI3 OFF OFF OFF ON ON ON ON OFF
DI3
share the same function.
DI4 OFF OFF OFF OFF OFF OFF OFF ON
DI3 40
+5V
* If all of the contact inputs are set to OFF,
DI4
the controller uses the immediately
+5V
preceding target setpoint.
DI4 39
Note: External Contact Input
DI5
AUTO when DI5=ON
If the power is turned on when the external
DI5 38
+5V
MAN when DI5=OFF
contact input is OFF, the mode (SPNO, R/L,
DI6
or A/M) existing before the power is turned
STOP when DI6=ON
DI6 37
+5V
RUN when DI6=OFF
off will be continued. (except for RUN/STOP)
DI7
Remote when DI7=ON
DI7 36
Local when DI7=OFF
COM
COM 20
Common
communication functions.
24
IMPORTANT
The controller is factory-set to the Single-loop Control.
Change the setting of the Control Output Type (OT1)
parameter to the Heating/Cooling Control.
Heating-side control output
SDA(-)
RDA(-)
27
SG
SG
PV input * Not configured at factory before shipment
See Initial Settings User’s Manual .
Remote input
21 +
25 RDB(+)
26
30
22 -
TC input
RTD input
NO
2
COM
3
37
36
20
1
41
31
21
11
2
42
32
22
12
PV input
0.4-2.0 V DC
signal
13
Two-wire
transmitter
14
12 b
250 Ω 4-20mA
Loop power
supply
14.518.0 V DC
4-20mADC
13 -
13 B
15
mV/V input
Note: Connecting a 250 Ω resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
13 -
Note: Connecting a 100 resistor to the terminals is optional.
Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
NOTE
Installation category (overvoltage category): II (IEC1010-1)
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Power supply
Power supply
L
8
N
3
43
33
23
13
4
44
34
24
14
5
45
35
25
15
6
46
36
26
16
7
47
37
27
17
8
48
38
28
18
9
49
39
29
19
16 +
10
50
40
30
20
17 -
* Factory-set to “PV retransmission.”
Retransmission output 1*
CAUTION
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
9
10
Heating-side
control output
External contact outputs
Relay
Alarm 1 output
DO1 6
Alarm 2 output
DO2 5
UT
Cooling-side control
DO4 34
output (Note)
Transistor
Alarm 4 output
DO6 32
No function
DO7 31
Common
COM 35
15 -
Default: Unspecified
retransmission type
Cooling-side control output
0-20mADC,
4-20mADC
14 +
Default: 4-20 mA DC
15 * The functions of the external contact outputs are the defaults for single-loop
heating/cooling control. To change the functions, reconfigure the contact output
registration setup parameters.
4-20 or
0-20 mA DC
14 +
15 -
14.5-18.0 V DC
(21 mA DC max.)
Default: 4-20 mA DC
16 +
17 -
14 +
15 V DC loop power supply*
0-20 mA DC
4-20 mA DC,
voltage pulse (12 V)
* Retransmission output 1 is not available if a
15 V DC loop power supply is used.
* If you define the cooling-side output as
current output, retransmission output 1 and
the 15 V DC loop power supply can no
longer be used.
* The functions of the external contact inputs are the defaults for single-loop heating/cooling control.
To change the functions, reconfigure the contact input registration parameters.
External contact inputs (Note)
Contact +5V
DI1
1.SP2.SP 3.SP4.SP 5.SP6.SP7.SP 8.SP
DI1 19
+5V
DI1 ON OFF ON OFF ON OFF ON OFF
DI2
DI2 OFF ON ON OFF OFF ON ON OFF
DI2 18
+5V
DI3 OFF OFF OFF ON ON ON ON OFF
DI3
DI4 OFF OFF OFF OFF OFF OFF OFF ON
DI3 40
+5V
* If all of the contact inputs are set to OFF,
DI4
Note: External Contact Input
the controller uses the immediately
Relay contact rating: 240 V AC, 1 A
+5V
preceding target setpoint.
DI4 39
If the power is turned on when the external
30 V DC, 1 A (resistance load)
Transistor contact rating: 24 V DC, 50 mA
contact input is OFF, the mode (SPNO, R/L,
DI5
AUTO when DI5=ON
DI5 38
+5V
or A/M) existing before the power is turned
MAN when DI5=OFF
DI6
off will be continued. (except for RUN/STOP)
STOP when DI6=ON
DI6 37
+5V
RUN when DI6=OFF
DI7
Remote when DI7=ON
DI7 36
Local when DI7=OFF
NOTE
COM
* The dual-loop type controller (UT750-5ⵧ) only
COM 20
Common
“Current output terminal ( 46 and 47 )” can be used for retransmission output 2.
COM 7
DO5 33
Retransmission
output 2*
0-20mADC,
4-20mADC
Voltage pulse (12 V)
Note: If you define the DO3 output as the cooling-side control output, the DO4 output
serves as the alarm 4 output. Inversely, if you define the DO4 output as the
cooling-side control output, the DO3 output serves as the alarm 3 output.
Cooling-side control
DO3 4
output (Note)
Alarm 3 output
Note: Select this option from the OT1 parameter.
* Retransmission output 2 is available
only when “relay” is selected as the
type of heating-side control output.
Current/voltage
pulse output
Allowable range: 100-240 V AC (10%)
(free voltage)
50/60 Hz shared
Common
38
12 +
13 -
Default: 1-5 V DC
Note: Select this option from the
OT1 parameter.
* When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint “41”).
11 A
12 +
1
䊏 Receiving 4-20 mA DC Current
Signals with the Controller
12 +
Specify in a range of
1-5 V DC, 0-2 V DC,
or 0-10 V DC.
Relay contact output
NC
39
12
* Wiring can only be carried out for
controllers with remote input.
28 RSB(+)
RSA(-)
40
External
resistor 100
(Note)
High performance
* Wiring can only be carried out
RS-485 communication for controllers with
29
18
䊏 15 V DC Power Supply Wired to Sensor in
Two-wire System Configuration
Communication 1 Communication 2
(PSL1)
(PSL2)
23 SDB(+)
19
Contact rating: 12 V DC, 10 mA or more
■ UT750 Single-loop Heating/Cooling Control (Model UT750-0䊐 or UT750 -5䊐)
RS-485 communication
Transistor contact
When switching among target setpoints 1 to 8: UT
Transistor contact
When switching among target setpoints 1 to 8: UT
* OT1 is a setup parameter.
You can change the settings of the parameter OT1 to change the control output type. See Initial Settings User’s Manual .
19
18
40
39
38
37
36
20
Contact rating: 12 V DC, 10 mA or more
Correspondence between parameter OT1 and heating-side output types/cooling-side output types
OT1=4
OT1=5
OT1=6
OT1=7
OT1=8
OT1=9
OT1=10
OT1=11
OT1=12
Heating side: Relay output
(terminals 1 , 2 and 3 )
Cooling side: Relay output
(terminals 4 and 7 )
Heating side: Voltage pulse output
(terminals 16 and 17 )
Cooling side: Relay output
(terminals 4 and 7 )
Heating side: Current output
(terminals 16 and 17 )
Cooling side: Relay output
(terminals 4 and 7 )
Heating side: Relay output
(terminals 1 , 2 and 3 )
Cooling side: Transistor output
(terminals 34 and 35 )
Heating side: Voltage pulse output
(terminals 16 and 17 )
Cooling side: Transistor output
(terminals 34 and 35 )
Heating side: Current output
(terminals 16 and 17 )
Cooling side: Transistor output
(terminals 34 and 35 )
Heating side: Relay output
(terminals 1 , 2 and 3 )
Cooling side: Current output
(terminals 14 and 15 )
Heating side: Voltage pulse output
(terminals 16 and 17 )
Cooling side: Current output
(terminals 14 and 15 )
Heating side: Current output
(terminals 16 and 17 )
Cooling side: Current output
(terminals 14 and 15 )
The types of control output, “relay output” and “voltage pulse output” shown in the table above refer to those of time proportional control.
To change to a relay output for on-off control, select “Relay Terminals” and change the setpoint of the proportional band to “0.”
IM 05D01B02-01E (2)