Download POWERTRONIX
Transcript
3.5 UPS IN FAULT CONDITIONS If the UPS experiences the fault, the normal status message will be replaced with the alarm one. An alarm message will differ depending on the type of fault which occurred. Activated sound signal can be switched off by pressing the ESC key. The ENTER (< >) key can be used to display the list of indications which let the operator to understand the meaning of the alarm. The <BACK or NEXT> keys can be used to scroll through all the active alarms. When the alarm cause disappears, the LCD will return to the default message. <ENTER> UPS ALARM ALARM CAUSE < BACK or NEXT> The possible alarms and associated with them help messages are listed below. ALARM MESSAGE INVERTER OFF INVERTER OVERLOAD STATIC SWITCH LOCKED BATTERY TEST FAILURE BATTERY PRE-ALARM STATIC SWITCH FAILURE MANUAL BYPASS ON MAINS OUT OF LIMITS BY-PASS OUT OF LIMITS EMERGENCY POWER OFF PARALLEL DATA EXCHANGE FAILURE BATTERY CHARGER FAILURE MEANING The load is no longer supplied by the inverter and subject to any mains failures The inverter is off due to an overload and the load is supplied by the reserve network After 3 unsuccessful automatic switching attempts from the reserve to inverter, the UPS blocks the static switch in the reserve network position Displayed whenever the periodic test on the battery fails for any reason At the battery voltage of around 345V the UPS warns the user of a low battery voltage At 320V discharging ends and the UPS switches off At least one of output phases is missing The manual bypass switch has been closed The mains voltage is out of allowed specification, it might be out of the range allowed by the system, or simply not present The reserve is out of allowed specification, it might be out of the range allowed by the system, or with incorrect cyclic direction, or not present Displayed whenever the E.P.O. button is pressed This alarm occurs when there is, for any reason, no data exchange between UPS units in parallel. It may be due to a missing or incorrect connection of one or more parallel fibers Battery charger doesn’t work properly or is not connected POWERTRONIX SpA reserves the right to modify this document without any notice R&D – PROCEDURA START-UP DT 0419 – E02 Pag. 25 di 41