CONNECTION OF THE PULSE OUTPUT
WIRING DIAGRAM
CAUTION: The pulse output contacts are rated at 27VAC 20mA/
27VDC 20 mA. Under no circumstances should this rating be
exceeded.
The pulse output connection is made via the two terminals marked
‘pulse’ (see wiring diagram). The contacts are volt-free and
therefore an external power source must be provided. Contacts
are normally open, and provide an output of 1 pulse per kWh. Pulse
duration (contacts closed) is 400/500 msec.
Pulse Ouput
3
INSTRUMENT PROGRAMMING
“WAIT” appears when the instrument is first powered up. After a few
seconds the power measurement will be displayed (the LED on the w key
is lit).
The programming key “ “ is located at the bottom left corner of the front
panel.
To enter into programming mode, simultaneously press the
w key
key and the
On the display the CT selection will appear.
A
5/5
Pressing the w key will scroll through the available CT ratios.
(See table.) When the desired selection is displayed, press the
programming key
to confirm, and exit setup mode.
S E LE C TAB LE C T
R ATIOS
NOTE: Unless the CT ratio is programmed the default value will be 5/5 (no
multiplier).
To reset the kWh value to zero press the
simultaneously
key and the
kWh
key
Once programmed, the setup and reset capability can be disabled by cutting
the jumper wire located under the CT input terminal cover. The cover may
be levered off with a small screwdriver to reveal the jumper to the right of
the CT input terminals. Once the jumper is cut, the reset and setup is
permanently disabled unless the jumper connection is remade.
4
TECHNICAL CHARACTERISTICS
Connection:
Inputs:
Input Overload:
Pulse Output:
Number of Scales:
Weight:
IP rating:
Temp Range:
Relative Humidity:
Condensation:
Isolation
Dims:
3 phase star or single phase
Voltage: 250V from 20 to 800 Hz
Current: 5A from 20 to 800 Hz
Voltage: Max 264 Vrms phase to neutral
Current; Max 20 Arms
Opto isolated volt free contact
Rating - 100mA 250 VAC
Value - 1 pulse per kWh
Duration - 400-500 msec
2 current scales
1 current voltage
270g.
Instrument = IP20 Front Panel = IP40
From -10oC to +40oC
RH Max 90%
Not permitted.
In accordance with group B VDE 0110
standards for 250 VACrms operating voltages.
70w x 57.5d x 90h (mm)
N.B: Do not expose the instrument display to direct sunlight.
5/5
500/5
25/5
600/5
40/5
750/5
50/5
800/5
60/5
1000/5
75/5
1200/5
80/5
1250/5
100/5
1500/5
120/5
1600/5
150/5
1800/5
200/5
2000/5
250/5
2500/5
300/5
3200/5
320/5
4000/5
400/5