Download EWCM9900
Transcript
13 EWCM9900 PROBES MENU Access to the Probes Menu takes place via the Main Display by pressing and holding down the RH function key. This Menu shows the values of the pressure transducers and the probes in the plant. Display of the values of the probes Scroll through the probe values with the UP and DOWN keys. PROBES SIG1 SIG1 SIG2 01/05 13.4 Bar 13.4 PSI 3.61 Bar PROBES SIG2 SIG3 SIG3 02/05 3.61 PSI 13.4 Bar 13.4 PSI PROBES PB1 PB1 PB2 03/05 15.6 °C 32.4 °F Err PROBES PB2 PB3 PB3 04/05 Err Err Err Note that each input has two separate values. SIG1/2/3 in Bar and PSI, PB1..4 in °C and °F. Configuration of analogue inputs The Probes Menu only allows you to view the analogue input values. To configure them, use the Configuration folder in the Parameters menu. The analogue inputs are configurable in pairs, with the following parameters: • 646 - Sig12 Probe Type SIG1/2 • 647 - Sig34 Probe Type SIG3 SIG4 is NOT present • 648 - Pb12 Probe Type PB1/2 • 649 - Pb34 Probe Type PB3/4 EWCM9900 default configuration: • The SIG1 transducer is used as a current suction transducer • The SIG2 transducer is not used • The SIG3 transducer is used as a current delivery transducer • PB1 is an NTC probe for measuring the internal temperature for the suction dynamic setpoint • PB2 is an NTC probe for measuring the external temperature for the delivery dynamic setpoint • PB3 is an NTC probe for measuring the internal subtemperature for the delivery dynamic setpoint • PB4 is an NTC probe - Not used Model EWCM9900 - configuration [501-tyP=501] • The SIG2 transducer is used as a suction transducer for circuit 2 when powered (place [654 - H402] =2) NOTE: • SIG1 and SIG2 are ALWAYS of the same type* (e.g. 4...20mA) • PB1 and PB2 are ALWAYS of the same type* (e.g. NTC) • PB3 and PB4 are ALWAYS of the same type* (e.g. digital input) * in other words, configurable in pairs. See the wiring diagrams. Pressure transducers resolution The resolution of transducers SIG1 and SIG2 is settable by parameter: • 650 - HSig1 SIG1 High Precision (0= No, 1 = Yes) • 651 - HSig2 SIG2 High Precision (0= No, 1 = Yes) The default setting is High Precision (1 = Yes): • Suction: in hundredths of bar / tenths of PSI • Delivery: in tenths of bar / tenths of PSI Also see the table at the bottom of the Value Displays page. Analog inputs calibration Analog inputs calibration can be set by parameters: 655 - CALSIg1 Calibration SIG1 bar 655 - CALSIg1 Calibration SIG1 PSI 656 - CALSIg2 Calibration SIG2 bar 656 - CALSIg3 Calibration SIG3 PSI 656 - CALSIg3 Calibration SIG3 bar 656 - CALSIg2 Calibration SIG2 PSI 659 - CALPb1 Calibration PB1 °C 659 - CALPb1 Calibration PB1 °F ... 662 - CALPb4 Calibration PB4 °C 662 - CALPb4 Calibration PB4 °F Note that each parameter can be given a double calibration depending on the unit of measurement. The calibration is significant when analogue inputs are configured as digital. Probe errors If the pressure probe/transducer is in error, the message Err appears in place of its value. VALUE DISPLAYS resolution of the regulation and accordingly the display is determined by the following table: Example Case of two suction circuits, shared drainage system Unit of measurement Bar PSI Resolution Suction* 0,01 0,1 Resolution Discharge** 0,1 1 Range -1999...1999 -1999...1999 Unit of measurement Resolution Suction 1* Bar 3.69 PSI 53.5 Resolution Suction 2* 3.69 53.5 Resolution Delivery** 13.7 198 °C °F 0,1 0,1 0,1 0,1 -1999...1999 -1999...1999 °C °F 0.1 0.1 0.1 0.1 Range Note: * SIG1 Circuit suction 1; SIG2 Circuit suction 2 - if present - see par. [501-tyPE]=2 and [654 - H402] =2 **SIG3 delivery Note: If • 650 - HSig1 = 0 Unit of measurement Bar PSI we have Resolution Suction 0,1 1 Resolution Discharge 0,1 1 -1999...1999 -1999...1999 0.1 0.1