EWCM9900
PROBES MENU
Access to the Probes Menu takes place via the Main Display by pressing
and holding down the RH function key.
This Menu shows the values of the pressure transducers and the probes in
the plant.
Display of the values of the probes
Scroll through the probe values with the UP and DOWN keys.
PROBES
SIG1
SIG1
SIG2
01/05
13.4 Bar
13.4 PSI
3.61 Bar
PROBES
SIG2
SIG3
SIG3
02/05
3.61 PSI
13.4 Bar
13.4 PSI
PROBES
PB1
PB1
PB2
03/05
15.6 °C
32.4 °F
Err
PROBES
PB2
PB3
PB3
04/05
Err
Err
Err
Note that each input has two separate values.
SIG1/2/3 in Bar and PSI, PB1..4 in °C and °F.
Configuration of analogue inputs
The Probes Menu only allows you to view the analogue input values. To
configure them, use the Configuration folder in the Parameters menu.
The analogue inputs are configurable in pairs, with the following
parameters:
• 646 - Sig12
Probe Type SIG1/2
• 647 - Sig34
Probe Type SIG3
SIG4 is NOT present
• 648 - Pb12
Probe Type PB1/2
• 649 - Pb34
Probe Type PB3/4
EWCM9900 default configuration:
• The SIG1 transducer is used as a current suction transducer
• The SIG2 transducer is not used
• The SIG3 transducer is used as a current delivery transducer
• PB1 is an NTC probe for measuring the internal temperature for the
suction dynamic setpoint
• PB2 is an NTC probe for measuring the external temperature for the
delivery dynamic setpoint
• PB3 is an NTC probe for measuring the internal subtemperature for the
delivery dynamic setpoint
• PB4 is an NTC probe - Not used
Model EWCM9900 - configuration [501-tyP=501]
• The SIG2 transducer is used as a suction transducer for circuit 2 when
powered (place [654 - H402] =2)
NOTE:
• SIG1 and SIG2 are ALWAYS of the same type* (e.g. 4...20mA)
• PB1 and PB2 are ALWAYS of the same type* (e.g. NTC)
• PB3 and PB4 are ALWAYS of the same type* (e.g. digital input)
* in other words, configurable in pairs. See the wiring diagrams.
Pressure transducers resolution
The resolution of transducers SIG1 and SIG2 is settable by parameter:
• 650 - HSig1
SIG1 High Precision (0= No, 1 = Yes)
• 651 - HSig2
SIG2 High Precision (0= No, 1 = Yes)
The default setting is High Precision (1 = Yes):
• Suction: in hundredths of bar / tenths of PSI
• Delivery: in tenths of bar / tenths of PSI
Also see the table at the bottom of the Value Displays page.
Analog inputs calibration
Analog inputs calibration can be set by parameters:
655 - CALSIg1
Calibration SIG1 bar
655 - CALSIg1
Calibration SIG1 PSI
656 - CALSIg2
Calibration SIG2 bar
656 - CALSIg3
Calibration SIG3 PSI
656 - CALSIg3
Calibration SIG3 bar
656 - CALSIg2
Calibration SIG2 PSI
659 - CALPb1
Calibration PB1 °C
659 - CALPb1
Calibration PB1 °F
...
662 - CALPb4
Calibration PB4 °C
662 - CALPb4
Calibration PB4 °F
Note that each parameter can be given a double calibration depending on
the unit of measurement.
The calibration is significant when analogue inputs are configured as digital.
Probe errors
If the pressure probe/transducer is in error, the message Err appears in
place of its value.
VALUE DISPLAYS
resolution of the regulation and accordingly the display is
determined by the following table:
Example
Case of two suction circuits, shared drainage system
Unit of
measurement
Bar
PSI
Resolution
Suction*
0,01
0,1
Resolution
Discharge**
0,1
1
Range
-1999...1999
-1999...1999
Unit of measurement Resolution
Suction 1*
Bar
3.69
PSI
53.5
Resolution
Suction 2*
3.69
53.5
Resolution
Delivery**
13.7
198
°C
°F
0,1
0,1
0,1
0,1
-1999...1999
-1999...1999
°C
°F
0.1
0.1
0.1
0.1
Range
Note:
* SIG1 Circuit suction 1; SIG2 Circuit suction 2 - if present - see
par. [501-tyPE]=2 and [654 - H402] =2
**SIG3 delivery
Note:
If • 650 - HSig1 = 0
Unit of
measurement
Bar
PSI
we have
Resolution
Suction
0,1
1
Resolution
Discharge
0,1
1
-1999...1999
-1999...1999
0.1
0.1