IODDTs and Device DDTs for Analog Modules Forcing a Value with the Animation Tables To force a DDT value in an animation table proceed as follows: Step Action 1 Select the chosen analog channel. 2 Set the FORCED_VALUE parameter value of the selected channel to the chosen value, for details on how to set a value, refer to chapter Modification Mode (see Unity Pro, Operating Modes). 3 Set the FORCE_CMD parameter to 1. 4 Result: Check that forcing is applied: FORCED_STATE needs to be equal to 1 VALUE = FORCED_VALUE Unforcing a Value with the Animation Tables To unforce a DDT value in an animation table proceed as follows: Step Action 1 Select the chosen analog channel. 2 Set the FORCE_CMD parameter to 0. 3 Result: Check that forcing is released: FORCED_STATE needs to be equal to 0 VALUE = TRUE_VALUE 35011978 10/2014 261