Download FactoryTalk View Machine Edition User`s Guide
Transcript
2. Specify these trigger values and alarm messages for the alarm trigger: Bit in the array (bit address) Bit position Trigger value Message 00 01 02 1 2 3 1 2 3 The motor has lost power. The motor has stopped. The overload switch has lost power. At run time, if power to the motor is lost, the programmable controller changes all three bit values from 0 to 1, but FactoryTalk View generates the first alarm message only (since bit 00 is the lowest—that is, least significant—bit in alarm). If the operator acknowledges the first alarm and power is not yet restored, the second alarm is generated, and so on. Tips for using array tags You can use these tag data types for array tags: Data type Number of bits Byte 8 Integer 16 Word 16 Long Integer 32 Double Word 32 The right column shows the number of bits for each data type. This is useful for helping to determine how many data elements to address to achieve the required number of bits. To create an array tag, specify how many elements to use, beginning with the first element at the tag’s address. For example, if you want to monitor 128 bit positions for an alarm trigger, and you are using the Long Integer data type, you would append the modifier [4] to the tag name (because 4 x 32 = 128). For detailed information about tag syntax, see page 9-16. You cannot use HMI tags for array tags. You must use data server tags for array tags. 9-15 • • • • • 9 • Setting up alarms