Download User Manual
Transcript
HGM7200/HGM7100 AUTO START MODULE 8.4 Selection of sensors (form 4) No. 1 2 3 Temperature sensor Pressure sensor Oil level sensor Description 0 not used 1 defined resistance curve 2 defined 4-20mA curve 3 VDO 4 CURTIS 5 VOLVO-EC 6 DATCON 7 SGX 8 SGD 9 SGH 10 PT100 11-15 reserved 0 not used 1 defined resistance curve 2 defined 4-20mA curve 3 VDO 10Bar 4 CURTIS 5 VOLVO-EC 6 DATCON 10Bar 7 SGX 8 SGD 9 SGH 10-15 reserved 0 not used 1 defined resistance curve 2 defined 4-20mA curve 3 SGD 4 SGH 5-15 reserved Remark Defined resistance’s scope is 0~6KΩ, default is SGX kind sensor. Defined resistance’s scope is 0~6KΩ, default is SGX kind sensor. Defined resistance’s scope is 0~6KΩ, default is SGH kind sensor. Note, user should make special declare when order controller if your genset equip for sensor of 4-20mA. 8.5 Conditions of start successfully selection No. 0 1 2 3 4 Setting description Gens frequency Speed sensor Speed sensor + Gens frequency Oil pressure Oil pressure + Gens frequency HGM7200/7100 Series Generator Controller ISSUE2010-12-15 Version1.1 Page 50 of 67