Download Zelio-Logic
Transcript
3. Fast Input Function "FILT." This function allows faster detection of changes in states on the inputs. This mode should only be used when necessary as it makes the smart relay’s inputs more sensitive to interference and signal bounce. Two choices are available: "FAST" and "SLOW". This function is available on DC smart relays. Note: This selection can only be made when the smart relay is set to STOP. By default, smart relays are configured to run in "SLOW" mode. References Filtering SR1A121BD Standard discrete input Analog inputs ON->OFF 5 ms 5 ms OFF->ON 3 ms 3 ms ON->OFF 0.5 ms Rated: 0.3 ms Max.: 0.5 ms OFF->ON 0.3 ms Rated: 0.2 ms Max.: 0.3 ms SLOW SR1B121BD SR1A221BD SR1B221BD Switching FAST The other (AC) modules only have one set filtering value that cannot be changed and which is dependent on the supply voltage. Refer to the technical characteristics provided in the Catalog. Smart Relay - Chapter 3 27