Download Volume 3 Section 2
Transcript
Chapter 10 Fire Safety Equipment Volume 3 Section 2 Part 3 BA 72/03 Fire Protection (and Gas Detection) Systems Description of Typical Equipment and Access Arrangements 10.26 Selected rooms in tunnel service buildings, enclosed sumps and other hazardous areas are afforded fire protection (see BS 5839: Part 1: 1988) and, where appropriate, gas detection. Plant room automatic fire extinguishing systems and enclosed-sump foam flooding systems are controlled and monitored through their respective fire control panels. Condition-status and alarms are relayed to the tunnel SCADA system, as appropriate. 10.27 Figure 10.1 shows a typical tunnel panel containing nitrogen foam and sump gas-detection equipment. 10.28 Automatic gas-discharge fire-extinguisher and extraction systems are normally installed in rooms within the tunnel service buildings that contain operational safety-related equipment, typically the high and low-voltage electrical switchgear, battery, computer and communications equipment rooms. Older systems may still use Halon gas, now prohibited from new installations. Installations that are more recent may use carbon dioxide (CO2). The most recent systems use synthetic gases mixed with nitrogen/argon that, unlike CO2, are breathable in the concentrations concerned. 10.29 Gas detection systems are sited in locations where measurements of gas may be required: eg cable chambers, sumps and draw-pits, tunnel service buildings and control and switch rooms. Different gases may be measured, typically oxygen and hydrocarbons. The systems trigger events to contain the situation once a set percentage of the lower explosive limit (LEL) has been passed. Typically pumps are inhibited when concentrations reach 30% LEL and then a nitrogen foam flooding system is initiated. In service buildings, when 20% LEL is reached, alarms and automatic fire extinguishers are triggered and at 30% LEL the gas extraction fan is inhibited. 10.30 A nitrogen-foam flooding system comprises a number of nitrogen gas cylinders, a foam generating set, a control system and a number of foam-generator nozzles. The foam-generator nozzles are installed within the sump and are connected by pipework to the foam-generating set, normally located in a tunnel panel. A bore closure may be required to safely access the foam generating set. May 2003 10.31 Care should be taken to ensure that whole systems are tested periodically, where for example servicing and testing of parts of the system are scheduled at different times or undertaken by different contractors. Maintenance of foam flooding systems 10.32 Maintenance should be in accordance with the manufacturer’s recommendations. Typically at intervals of 3 months, the panels should be cleaned to ensure readability and checked to ensure they are clear of alarms. Checks should also be made for signs of deterioration of flexible pipework, and signs of corrosion, damage or overheating of all connectors and earths. Nitrogen cylinder pressure should be determined and all cylinders checked for security. 10.33 A test fire should be carried out together with a purging of foam, in accordance with the manufacturer’s recommendations, at intervals typically of 12 months. Care must be taken to ensure that no one is within or adjacent to the sump when this test is conducted. Maintenance of gas detectors 10.34 This should be in accordance with the manufacturer’s recommendations. The services of a specialised contractor are normally required. Typically, the operation of the systems should be tested, electrical connections checked and the sensors re-calibrated at intervals of 3 months: sensors should be replaced at intervals, typically of 12 months. Maintenance of automatic fire extinguishers 10.35 Inspection of the automatic gas discharge and extraction system should be carried out at intervals typically of 3 months. Specialised servicing of the system, in accordance with the manufacturer’s recommendations, should be carried out at the same time, together with testing which may require the control system to be manually overridden. Maintenance of fire detection systems 10.36 This should be in accordance with the manufacturer’s recommendations. 10.37 Testing and maintenance of the fire alarm and detection system should be carried out in accordance with BS 5839: Part 1. This requires daily checks of panels and log books and selective system and equipment testing at weekly, 3-monthly, yearly and 5-yearly intervals. 10/3