Download Installation & User Manual V2.05
Transcript
YOUR SECURITY IS OUR PRIORITY Other products from GSD Contents Initial Setup 2 Installation Diagrams 4 Wiring Diagrams 6 Enrolling Door Controls 13 Wi-Pin & Prox Wi-Pin Wi-Prox Global Security Devices Ltd: No.3 Broomhill Business Complex, Tallaght, Dublin 24, Ireland, Phone: +353 (1) 524 2691, Email: info@globalsecurity.ie www.globalsecurity.ie Installation & User Manual V2.05 2 Initial Setup Initial Setup Technical Specs Power Supply Current consumption Current consumption with load (max) Relay Contact Rating Operating Temperature Moisture Resistance Dimensions - Flush Mount - Surface Mount Number of Users 12V DC 70mA 100mA 5 Amps /240V ac -20 C to +60 C IP 67 W. 87mm D. 21mm H. 119mm W. 87mm D. 35mm H. 119mm 20000 Initial Installation The Door Control should be Factory Defaulted after installation. This will restore all default settings to the Door Control and will unenrol it from any existing GSD Controller. The Door Control will then start to scan and enrol on a GSD controller. Refer to the section ‘Enrolling Door Controls’ for instructions on how to configure the GSD Windows Software. Restoring Factory Settings - Wi-Prox Step 1 Present Programming Card 2 Times 2 Present Any Card Once Example: X key then Engineer Code + Code = 55 Programming Card x 2 AnyCard x1 Note: Add a programming card to the Wi-Prox Door Control. The Door Control must be disabled first if it has been enrolled onto a GSD Network Controller. Follow the below method to add a programming card to the Door Control. Adding a Programming Card Adding a Programming Card Step Description 1 Remove security caps and power down unit. 2 Power up unit and Present Any Card 2 times immediately. This card is now the Programming Card for the unit. Refit security caps Restoring Factory Settings - Wi-Pin&Prox, Wi-Pin Code Description 55 Restore Factory Default Settings Description AnyCard x2 + Note: The Door Control can not be defaulted while enrolled onto a GSD network controller. The Door Control must first be disabled using the GSD windows software. If the Door Control is enrolled onto the GSD Network Controller then the Default Engineer code will be set by the GSD windows Software. If Engineer Code is lost, Ensure the Door Control is disabled using the GSD windows software , then remove the Security Caps (see page 5) and hold down the X key during power-up and enter the default Engineer Code ‘6666’ immediately.This will restore the factory settings. Factory Default PIN codes The following PIN codes are the Factory Default Settings: - The Default Engineer code is ‘6666’ - User PIN ‘1111’ Note: The User PIN ’1111’ is deactivated when the Door Control is enrolled onto a GSD Network Controller. 3 4 Installation Diagrams Installation Diagrams 5 Flush Mounting When Surface Mounting the Door Control a Surface Mount Collar is required. - Fix Surface Mount Collar to wall, ensure arrow is pointing upwards Door Control is mounted to electrical pattress box using security screws provided. Both Security Caps are then clipped onto Door Control. Surface Mounting After fixing Surface Mount Collar to wall (as above) and wiring is complete as per wiring diagrams on pages 6-11, the Door Control may then be screwed to Surface Mount Collar using security screws provided. Both Security Caps are then clipped onto the Door Control. To attach Security Caps: Simply align the tabs into holes and push on until click is heard. To release Security Caps push a screwdriver into slots on the side and pull forward. Security Caps To attach Security Caps: Simply align the tabs into holes and push on until click is heard. 6 Wiring Diagrams Wiring Diagrams 7 Slave Reader connections Standard connections External Reader 12V Red & Brown 12V Linear Power supply Data1/Clock 12V Linear Power supply Yellow & White 0V 12V 12V 16V Varistor Data0/Data 16V Varistor Door Contact Door Contact 12V 0V NO COM NC IP3 IP2 IP1 OP1 OP2 Door MagLock IP3 IP2 IP1 OP1 OP2 A B TAMP TAMP A B TAMP TAMP Door MagLock 12V 0V NO COM NC 0V 0V 0V 0V Door Exit Button Door Exit Button Select the Slave Reader option from the drop-down list for IP3 on the PC application for this Door Control. Break Glass Unit Break Glass Unit 0V 12 - 24 VAC 16V Varistor 0V 12 - 24 VAC 12V 0V NO COM NC 12 - 24 VAC Wiring for StrikeLock only using 12 - 24VAC supply 16V Varistor Note: All OV shown in the diagram are connected to 0V OV of the Door Control. 12V 0V NO COM NC 12 - 24 VAC Wiring for StrikeLock only using 12 - 24VAC supply 0V Note: All OV shown in the diagram are connected to OV of the Door Control. 8 Wiring Diagrams Wiring Diagrams 9 Fire Alarm Override Alarm Panel connections Door Exit Button Fire Alarm Panel 12V Linear Power supply 12V Linear Power supply 0V Door Contact 12V 0V 12V 16V Varistor 16V Varistor IP3 IP2 IP1 OP1 OP2 Door MagLock A B TAMP TAMP 12V 0V NO COM NC 0V IP3 IP2 IP1 OP1 OP2 Door MagLock A B TAMP TAMP 12V 0V NO COM NC Door Contact Arm Output (N/O) 0V Arm Alarm Input 0V 0V Door Exit Button Alarm Panel Notes: Common OV from the Intruder Alarm Panel and the OV from the Door Control to avoid any ground loop issues. Break Glass Unit 12V 0V NO COM NC Wiring for StrikeLock only using 12 - 24VAC supply Break Glass Unit 12 - 24 VAC Select the Panel Alarm option from the drop-down list for IP3 on the PC application for this Door Control. 12 - 24 VAC FireAlarm Panel Notes: Common OV from the Fire Alarm Panel and the OV from the Door Control to avoid any ground loop issues. When the fire alarm is activated (0V removed from IP3) the door will be opened. Only the Manager User can activate/deactivate the Alarm Panel. When the Alarm Panel is activated all other users are locked out. 12 - 24 VAC 16V Varistor Alarm Panel 16V Varistor Note: All OV shown in the diagram are connected to 0V OV of the Door Control. 12V 0V NO COM NC 0V Select the Fire Alarm Override option from the drop-down list for IP3 on the PC application for this Door Control. 12 - 24 VAC Wiring for StrikeLock only using 12 - 24VAC supply 0V Note: All OV shown in the diagram are connected to OV of the Door Control. 10 Wiring Diagrams Wiring Diagrams 11 Sounder & Follow Relay Interlock connections Door Contact 12V Linear Power supply 12V Linear Power supply - Fire Alarm Override - Lock Door - Card and Pin - Card or Pin 0V Door Exit Button 12V 16V Varistor 16V Varistor IP3 IP2 IP1 OP1 OP2 A B TAMP TAMP Door MagLock 0V 0V Interlock IP from Interlock OP on 2nd Door 0V Door Exit Button 0V The Follow Relay option is enabled on OP1 when any of the following options are selected on IP3 on the PC application for a Door Control: Break Glass Unit - Fire Alarm Override - Lock Door - Card and Pin - Card or Pin 12 - 24 VAC IP3 IP2 IP1 OP1 OP2 Door MagLock Interlock OP to Interlock IP on 2nd Door Select the Interlock Input option from the drop-down list for IP3 on the PC application for this Door Control. Break Glass Unit 12V 0V NO COM NC A B TAMP TAMP 12V 0V NO COM NC 16V Varistor Door Contact 12V 0V Follow Relay 12V 12 - 24 VAC 12V 0V NO COM NC 12 - 24 VAC Wiring for StrikeLock only using 12 - 24VAC supply 16V Varistor Note: All OV shown in the diagram are connected to 0V OV of the Door Control. 12V 0V NO COM NC Sounder 12 - 24 VAC Wiring for StrikeLock only using 12 - 24VAC supply 0V Note: All OV shown in the diagram are connected to OV of the Door Control. 12 Wiring Diagrams Enrolling Door Controls Wired 485 connections Adding Door Controls Overview Step Description Door Contact 12V Linear Power supply 1 Install and Wire each Door Control 2 Default each Door Control 3 On PC application - Doors Tab Click on Add New Door to add a new door to the system 4 Enrolling On a New System Install: On PC application - Controller Tab - Wireless Network Click on Create New Network. Continue with Step 5 5 Enrolling On an Existing System: On PC application - Controller Tab - Wireless Network Click Allow Doors to Join. 6 Each new Door Control will beep the next available address on the system 7 Press a key or present a Fob to assign this address to any Door Control. Continue with steps 6 & 7 until all new Door Controls are assigned an address on the system. 8 After all Door Controls are assigned an address: On PC application - Controller Tab - Wireless Network Click on Secure Network. This secures the wireless network. 9 On PC application - Doors Tab, Configure each Door Control with desired settings. 0V Door Exit Button 12V 16V Varistor 12V 0V NO COM NC IP3 IP2 IP1 OP1 OP2 0V A B TAMP TAMP Door MagLock 0V Break Glass Unit Volt Free Tamper Contacts 1 and 2 Note : Used ONLY for Wired 485 Network Connections. B A 0V 12 - 24 VAC 16V Varistor 12V 0V NO COM NC 12 - 24 VAC Wiring for StrikeLock only using 12 - 24VAC supply 0V Note: All OV shown in the diagram are connected to OV of the Door Control. 13 14 Enrolling Door Controls Enrolling Door Controls Adding Door Controls Assigning a Door Address on Wireless Network Step 2 1 5 1 Description On the Controller screen: Click ‘Allow Doors to Join this Controller’ All Door Controls that don’t have an address start to beep out the next available address. The Keys will also illuminate to indicate the address. e.g. Keys 1 & 5 will be ON for address number 15. 2 Hit any key on the ‘beeping’ Door Control to assign this address. Present a Card on the ‘beeping’ Proximity unit to assign this address. When a Door Control is assigned an address, all unassigned Door Controls will start to beep the next available address. 3 Step Description 1 Click the Doors Icon on the left hand toolbar 2 Click ‘Add New Door’ 3 The Door is added to the Controller. Assigning a Door Address on a Wired 485 Network Step 4 5 When all doors are assigned: Click ‘Secure Network’ Configure the required Door settings : Door Timers, Alarm Options, Door Options, Timed Actions, Inputs & Outputs. 1 Description Right Click on the Controller Icon & select ‘Manually Assign Addresses’ Click ‘Save’ to transmit the changes to the GSD Controller. Follow Step 2 above to complete the process. 15