Installation & User Manual
V2.05
2
Initial Setup
Initial Setup
Technical Specs
Power Supply
Current consumption
Current consumption with load (max)
Relay Contact Rating
Operating Temperature
Moisture Resistance
Dimensions - Flush Mount
- Surface Mount
Number of Users
12V DC
70mA
100mA
5 Amps /240V ac
-20 C to +60 C
IP 67
W. 87mm D. 21mm H. 119mm
W. 87mm D. 35mm H. 119mm
20000
Initial Installation
The Door Control should be Factory Defaulted after installation. This will restore all
default settings to the Door Control and will unenrol it from any existing GSD
Controller.
The Door Control will then start to scan and enrol on a GSD controller.
Refer to the section ‘Enrolling Door Controls’ for instructions on how to configure
the GSD Windows Software.
Restoring Factory Settings - Wi-Prox
Step
1
Present Programming Card 2 Times
2
Present Any Card Once
Example:
X key then
Engineer
Code
+
Code = 55
Programming
Card x 2
AnyCard
x1
Note: Add a programming card to the Wi-Prox Door Control. The Door
Control must be disabled first if it has been enrolled onto a GSD Network
Controller.
Follow the below method to add a programming card to the Door Control.
Adding a Programming Card
Adding a Programming Card
Step
Description
1
Remove security caps and power down unit.
2
Power up unit and Present Any Card 2 times
immediately. This card is now the Programming
Card for the unit. Refit security caps
Restoring Factory Settings - Wi-Pin&Prox, Wi-Pin
Code Description
55
Restore Factory Default Settings
Description
AnyCard
x2
+
Note: The Door Control can not be defaulted while enrolled onto a GSD network
controller. The Door Control must first be disabled using the GSD windows
software.
If the Door Control is enrolled onto the GSD Network Controller then the
Default Engineer code will be set by the GSD windows Software.
If Engineer Code is lost, Ensure the Door Control is disabled using the GSD
windows software , then remove the Security Caps (see page 5) and
hold down the X key during power-up and enter the default Engineer
Code ‘6666’ immediately.This will restore the factory settings.
Factory Default PIN codes
The following PIN codes are the Factory Default Settings:
- The Default Engineer code is ‘6666’
- User PIN ‘1111’
Note: The User PIN ’1111’ is deactivated when the Door Control is enrolled
onto a GSD Network Controller.
3
4
Installation Diagrams
Installation Diagrams
5
Flush Mounting
When Surface Mounting the Door Control
a Surface Mount Collar is required.
- Fix Surface Mount Collar to
wall, ensure arrow is
pointing upwards
Door Control is mounted to electrical pattress box using security
screws provided. Both Security Caps are
then clipped onto Door Control.
Surface Mounting
After fixing Surface Mount Collar to wall
(as above) and wiring is complete as per
wiring diagrams on pages 6-11, the Door
Control may then be screwed to
Surface Mount Collar using
security screws provided.
Both Security Caps are
then clipped onto the Door
Control.
To attach Security Caps: Simply
align the tabs into holes and push
on until click is heard.
To release Security Caps push a
screwdriver into slots on the side
and pull forward.
Security Caps
To attach Security Caps: Simply
align the tabs into holes and push
on until click is heard.
6 Wiring Diagrams
Wiring Diagrams
7
Slave Reader connections
Standard connections
External
Reader
12V
Red & Brown
12V Linear
Power supply
Data1/Clock
12V Linear
Power supply
Yellow & White
0V
12V
12V
16V
Varistor
Data0/Data
16V
Varistor
Door
Contact
Door
Contact
12V
0V
NO
COM
NC
IP3
IP2
IP1
OP1
OP2
Door
MagLock
IP3
IP2
IP1
OP1
OP2
A
B
TAMP
TAMP
A
B
TAMP
TAMP
Door
MagLock
12V
0V
NO
COM
NC
0V
0V
0V
0V
Door
Exit Button
Door
Exit Button
Select the Slave Reader option
from the drop-down list
for IP3 on the PC application
for this Door Control.
Break Glass
Unit
Break Glass
Unit
0V
12 - 24 VAC
16V
Varistor
0V
12 - 24 VAC
12V
0V
NO
COM
NC
12 - 24 VAC
Wiring for StrikeLock only using 12 - 24VAC supply
16V
Varistor
Note: All OV shown in the
diagram are connected to
0V
OV of the Door Control.
12V
0V
NO
COM
NC
12 - 24 VAC
Wiring for StrikeLock only using 12 - 24VAC supply
0V
Note: All OV shown in the
diagram are connected to
OV of the Door Control.
8
Wiring Diagrams
Wiring Diagrams
9
Fire Alarm Override
Alarm Panel connections
Door
Exit Button
Fire Alarm
Panel
12V Linear
Power supply
12V Linear
Power supply
0V
Door
Contact
12V
0V
12V
16V
Varistor
16V
Varistor
IP3
IP2
IP1
OP1
OP2
Door
MagLock
A
B
TAMP
TAMP
12V
0V
NO
COM
NC
0V
IP3
IP2
IP1
OP1
OP2
Door
MagLock
A
B
TAMP
TAMP
12V
0V
NO
COM
NC
Door
Contact
Arm Output (N/O)
0V
Arm Alarm Input
0V
0V
Door
Exit Button
Alarm Panel Notes:
Common OV from the
Intruder Alarm Panel
and the OV from the
Door Control to avoid
any ground loop issues.
Break Glass
Unit
12V
0V
NO
COM
NC
Wiring for StrikeLock only using 12 - 24VAC supply
Break Glass
Unit
12 - 24 VAC
Select the Panel Alarm option
from the drop-down list
for IP3 on the PC application
for this Door Control.
12 - 24 VAC
FireAlarm Panel Notes:
Common OV from the
Fire Alarm Panel
and the OV from the
Door Control to avoid
any ground loop issues.
When the fire alarm
is activated (0V removed
from IP3) the door will
be opened.
Only the Manager User
can activate/deactivate
the Alarm Panel. When
the Alarm Panel is
activated all other users
are locked out.
12 - 24 VAC
16V
Varistor
Alarm Panel
16V
Varistor
Note: All OV shown in the
diagram are connected to
0V
OV of the Door Control.
12V
0V
NO
COM
NC
0V
Select the Fire Alarm Override option
from the drop-down list
for IP3 on the PC application
for this Door Control.
12 - 24 VAC
Wiring for StrikeLock only using 12 - 24VAC supply
0V
Note: All OV shown in the
diagram are connected to
OV of the Door Control.
10 Wiring Diagrams
Wiring Diagrams 11
Sounder & Follow Relay
Interlock connections
Door
Contact
12V Linear
Power supply
12V Linear
Power supply
- Fire Alarm Override
- Lock Door
- Card and Pin
- Card or Pin
0V
Door
Exit Button
12V
16V
Varistor
16V
Varistor
IP3
IP2
IP1
OP1
OP2
A
B
TAMP
TAMP
Door
MagLock
0V
0V
Interlock IP from
Interlock OP
on 2nd Door
0V
Door
Exit Button
0V
The Follow Relay option is enabled
on OP1 when any of the following
options are selected on IP3 on the
PC application for a Door Control:
Break Glass
Unit
- Fire Alarm Override
- Lock Door
- Card and Pin
- Card or Pin
12 - 24 VAC
IP3
IP2
IP1
OP1
OP2
Door
MagLock
Interlock OP to
Interlock IP on
2nd Door
Select the Interlock Input option
from the drop-down list
for IP3 on the PC application
for this Door Control.
Break Glass
Unit
12V
0V
NO
COM
NC
A
B
TAMP
TAMP
12V
0V
NO
COM
NC
16V
Varistor
Door
Contact
12V
0V
Follow
Relay
12V
12 - 24 VAC
12V
0V
NO
COM
NC
12 - 24 VAC
Wiring for StrikeLock only using 12 - 24VAC supply
16V
Varistor
Note: All OV shown in the
diagram are connected to
0V
OV of the Door Control.
12V
0V
NO
COM
NC
Sounder
12 - 24 VAC
Wiring for StrikeLock only using 12 - 24VAC supply
0V
Note: All OV shown in the
diagram are connected to
OV of the Door Control.
12 Wiring Diagrams
Enrolling Door Controls
Wired 485 connections
Adding Door Controls Overview
Step
Description
Door
Contact
12V Linear
Power supply
1
Install and Wire each Door Control
2
Default each Door Control
3
On PC application - Doors Tab
Click on Add New Door to add a new door to the system
4
Enrolling On a New System Install:
On PC application - Controller Tab - Wireless Network
Click on Create New Network.
Continue with Step 5
5
Enrolling On an Existing System:
On PC application - Controller Tab - Wireless Network
Click Allow Doors to Join.
6
Each new Door Control will beep the next available address on the
system
7
Press a key or present a Fob to assign this address to any Door
Control. Continue with steps 6 & 7 until all new Door Controls are
assigned an address on the system.
8
After all Door Controls are assigned an address:
On PC application - Controller Tab - Wireless Network
Click on Secure Network.
This secures the wireless network.
9
On PC application - Doors Tab,
Configure each Door Control with desired settings.
0V
Door
Exit Button
12V
16V
Varistor
12V
0V
NO
COM
NC
IP3
IP2
IP1
OP1
OP2
0V
A
B
TAMP
TAMP
Door
MagLock
0V
Break Glass
Unit
Volt Free
Tamper Contacts
1 and 2
Note : Used ONLY for
Wired 485 Network
Connections.
B
A
0V
12 - 24 VAC
16V
Varistor
12V
0V
NO
COM
NC
12 - 24 VAC
Wiring for StrikeLock only using 12 - 24VAC supply
0V
Note: All OV shown in the
diagram are connected to
OV of the Door Control.
13
14 Enrolling Door Controls
Enrolling Door Controls
Adding Door Controls
Assigning a Door Address on Wireless Network
Step
2
1
5
1
Description
On the Controller screen: Click ‘Allow Doors to Join this Controller’
All Door Controls that don’t have an address start to beep out the next
available address. The Keys will also illuminate to indicate the address.
e.g. Keys 1 & 5 will be ON for address number 15.
2
Hit any key on the ‘beeping’ Door Control to assign this address.
Present a Card on the ‘beeping’ Proximity unit to assign this address.
When a Door Control is assigned an address, all unassigned Door
Controls will start to beep the next available address.
3
Step
Description
1
Click the Doors Icon on the left hand toolbar
2
Click ‘Add New Door’
3
The Door is added to the Controller.
Assigning a Door Address on a Wired 485 Network
Step
4
5
When all doors are assigned: Click ‘Secure Network’
Configure the required Door settings : Door Timers, Alarm Options,
Door Options, Timed Actions, Inputs & Outputs.
1
Description
Right Click on the Controller Icon & select ‘Manually Assign Addresses’
Click ‘Save’ to transmit the changes to the GSD Controller.
Follow Step 2 above to complete the process.
15