Download User Manual
Transcript
Please note that all the steps will be disconnected if the power factor regulator detects a re-generative condition under Rotational (rot) or Automatic (Aut) switching program. Alarm Description Delay time Action Message Activate Deactivate Current THD exceed set *5 All steps thd 5 min 2.5 min THD Limit disconnected Current lower than 1% 10 s 5s Lol rated value Current exceed 110% of 2 min 1 min Hil rated value 5 voltage lower than * All steps 100 ms 5s LoU 295VAC of rated value *6 disconnected Voltage exceed 456VAC 15 min 7.5 min HiU *6 of rated value 15 min 7.5 min UCo All capacitors are connected and the power factor lower than set power factor 15 min 7.5 min OCo All capacitors are disconnected and the power factor higher than set power factor Auto C/K or rated step ESt measurement error. Manual setting required Automatic CT polarity ECt detection error *5- Automatic switching of steps are prohibited when this alarm occurred. *6- For 200 ~240V model, LoU is 170V & HiU is 264V 4.7 THD Limit This parameter specifies the limit of total harmonic distortion level before an alarm is activated (More information on section 6). This function can be disabled by setting the parameter to "oFF". 4.8 Procedure for Setting the Control Parameters Step 1: Select the required item by stepping through all the items using "MODE/SCOLL" key. The corresponding indicator of the selected item will be lit. For "Rated step" setting, the individual output can be selected via the "UP" or "DOWN" keys, the step indicator corresponds to the step number. Step 2: Press the "PROGRAM" key once, the indicator of the selected item will blink to indicate that the system is now in programming mode. Step 3: Use the "UP" or "DOWN" keys to select the desired value. Target power Factor STEP LED* 1 SET Cos C/K Setting Range Default Factory Setting 0.80 Ind - 0.80 Cap 0.98 Ind C/K Sensitivity SENSITIVITY Reconnection Time RECON TIME 0.03 - 1.20/AtC 5 - 300 s/step 5 - 240s Rated Step*2: Step 1 1 001- 002 - 003 - 004 - Step 2 2 005 - 006 - 008 - 012 - 000 - disable Blinks On Blinks On Blinks On Blinks On Blinks On Blinks - Blinks - During the power on start-up process, the power factor regulator, if programmed under Rotational or Automatic switching program, detects the CT polarity and correct it internally if the CT polarity is reversed. If the power factor regulator is set for Four-quadrant switching program, this feature is disabled. 8. Programming Lock AtC The power factor regulator is equipped with a programming lock to prevent inadvertent changes to the control parameters. If locked, all the control parameters can only be viewed at and cannot be changed without unlocking it first. 45 s/step 30s To lock or unlock, first ensure that the display is on the power factor display function mode, then press "PROGRAM" key once followed by "DOWN" key immediately. Hold the "DOWN" key until the numeric display flashes "LOC" or "CLr". "LOC" indicates the power factor regulator is locked and "CLr" indicates the regulator is unlocked. 016 RATED STEPS - 7. Automatic CT polarity detection To abort without saving the selected setting, press the "MODE/SCROLL" key. Indic ation LED Blinks Table 3: Alarm table Step 4: To save the selected value, press the "PROGRAM" key once, the indicator stop blinking and the setting is saved. Control Paramen ter Alarm outputs LED Relay Blinks On 001 ALA*3 - alarm ouput FAn*4 - fan output 9. Technic al D ata Step 14 Switching Program 14 SWITCH PROG THD Limit THD LIMIT n-A - rot - Aut - Fqr 0.20 - 3.00/ oFF 9.1 Auxiliary Supply Aut Supply voltage Operating Limits Consumption Frequency 0.50 *1- Under normal operation except for rated step display, the step indicator indicate step ON/OFF status *2- Number of steps depend on model *3- Only last output can be configured as alarm output *4- Last output can be configured as fan output, or second last output can be configured as fan output only when last output is configured as alarm output. : 200~240 VAC / 346 ~ 415 VAC : -15% + 10% : 10VA max : 50Hz or 60Hz 9.2 C urrent Input Rated current , ln Operatings Limits Rated Frequency Table 2: Parameters setting 4.9 Reset To Factory Default Setting To reset all programmable parameters to factory default, first power off the power factor regulator. Press the "UP" & "DOWN" keys simultaneously while turning on the power and holds it for more than 5 sec until the display flashes "dEF" for 3 sec. Now the power factor regulator is restored to factory default setting. : 5A : 0.05A - 6.5A : 50Hz or 60Hz 9.3 Relay Output Numbers of outputs : 6 / 8 / 12 / 14 ( PFR60 / PFR80 / PFR120/ PFR140) Contact arrangment : NO contact type Rated capacity : 5A 250VAC (Cos ϕ = 1) Max current for the : 12A continuous common terminals 5. Fan Output When the fan output is selected, the output will be energized with 9.4 C ontrol Range any capacitor bank switched ON. Power factor setting C/K setting Switching sensitivity Reconnection time for same step THD threshold Switching Program 6. Alarm Alarm conditions detected by the power factor regulator are indicated by the flashing "ALARM" light indicator. The last step of the regulator, if required, can also be selectively programmed as alarm contact in addition to the "ALARM" indicator. This additional alarm contact is normally open and it closes when alarm is activated. To view the alarm message, press the "MODE/SCROLL" key until the "ALARM" function is selected. The numeric display will show the alarm message as according to Table 3 below. If more than one alarm messages are recorded, press the "UP" or "DOWN" keys to view the others. The alarm indications are automatically reset to normal once the alarm conditions are restored. : 0.8 inductive - 0.8 capacitive : 0.03 - 1. 20 / Auto : 5 - 600 s/step : 5 - 240 s : 0.20 - 3.00 (20% - 300%) / OFF : Automatic / Automatic Rotate / Manual/ Four- quadrant Rated step coefficient : 0 / 1 / 2 / 3 / 4 / 6 / 8 / 12 /16 9.5 Mechanical Mounting : Panel mounting Dimension ( h X w X d) : 144mm X 144mm X 91mm Approximate weight : 1kg 3