Download FXCPU Structured Programming Manual

Transcript
FXCPU Structured Programming Manual
[Device & Common]
Error
code
5 Errors
5.2 FX1S/FX1N/FX1NC/FX2N/FX2NC PLCs
PLC
operation
at error
occurrence
Contents of error
Action
Operation error [M8067(D8067)]
6742
The measured value variation exceeds the limit.
(ΔPV < -32768 or 32767 < ΔPV)
6743
The deviation exceeds the limit.
(EV < -32768 or 32767 < EV)
6744
The integral result exceeds the limit.
(Outside the range from -32768 to 32767)
6745
The derivative value exceeds the limit due to the
derivative gain (KD) beyond the limit.
6746
The derivative result exceeds the limit.
(Outside the range from -32768 to 32767)
6747
The PID operation result exceeds the limit.
(Outside the range from -32768 to 32767)
<The PLC continues PID operation.>
The PLC continues operation with each parameter set to the
maximum or minimum value.
<Step response method>
The auto tuning result is improper.
<The PLC finishes auto tuning, and starts PID operation.>
• When auto tuning was finished, the difference between the
measured value at the start of auto tuning and the target value
was 150 or less.
• When auto tuning was finished, the difference between the
measured value at the start of auto tuning and the target value
was 1/3 or more.
Check the measured value and target value, and then execute tuning
again.
<Step response method>
Auto tuning operation direction mismatch
<The PLC forcibly finishes auto tuning, and does not start PID
operation.>
The operation direction estimated from the measured value at the
start of auto tuning did not agree with the actual operation direction
caused by the output for auto tuning.
Correct the relationship among the target value, output value for auto
tuning and measured value, and then execute auto tuning again.
6752
<Step response method>
The auto tuning operation is improper.
<The PLC finishes auto tuning, and does not start PID operation.>
The PLC did not execute auto tuning correctly because the set value
fluctuated during auto tuning.
Set the sampling time to a value sufficiently longer than the output
change cycle, or set the input filter constant to a larger value.
After changing the setting, execute auto tuning again.
6760
Sum check error in the ABS data sent from the servo Check the connection to the servo and parameter setting.
6750
6751
262
Continues
operation