Download Code of Practice
Transcript
In order to meet the minimum requirement of all (active Vapour Recovery) pump types the following recommendations should be used: That Qmax shall be adjusted to match the maximum vapour flow rate provided by the VR system. The manufacturer’s instructions for measuring fuel flow and vapour flow rates shall be used. Qmax for Stage II VR is as specified in the efficiency type approval certificate available from the OEM, or less if limited by the actual dispenser possible fuel flow rate. Note that, the maximum Qmax for a dispenser is specified as part of its Metrology approvals and typically recorded on the Approvals Plate, this must never be exceeded. 12.5 Calibration Calibration of the Stage II VR system will make sure that the correct levels of vapours are being recovered, as specified and implemented by the UK regulations and set out below for clarity. Volume: Petrol Ratio Limits. Reference should be made to most recent issue of DEFRA PGN1/14(06): Type approval V/P 95% to 105%. Initial Calibration on site V/P 95% to 105%. Annual check (Without monitoring system installed) V/P 95% to 105%. Three yearly check (When monitoring system is installed) V/P 95% to 105%. Automatic Monitoring Systems - see section 8.2. When the Stage II VR system passes the test then the installer will complete a “Compliance Certificate” of the complete system and supply the retailer with one copy for site records. FEF Stage II VR COP Issue 1.2 - 13/03/2008 Page 26 of 32