Download User manual
Transcript
AI-02UI-uso-e 11-10-2011 15:37 Pagina 2 Hardware Set-up Value Hexadecimal rotary switches, service and I/O LEDs LED Status ON RUN Blinking Single flash OFF ON Single flash ERR Double flash Triple flash OFF ON ST Blinking Single flash OFF PWR ON OFF Top view • Hi ide nt s Fro • Lo Negative screwdriver 0.4 x 2.5 mm • • Meaning Operational Pre-operational (CANopen) STOPPED Device in RESET state BUS OFF Warning limit reached Error Control Event Sync Error (CANopen) No error. Device working DIAG Error INIT and DIAG running Baud rate setting Module OK and ready Module Power Supply ON Module Power Supply OFF Sensor Decimal Value type digits TCJ (default) 0x01 2 PT1000 TCK 0x02 2 PT100 2w TCL 0x03 2 PT100 4w TCN 0x04 2 0...10V TCR 0x05 2 0...150mV TCS 0x06 2 4...20mA TCT 0x07 2 0...20mA PT100 3w 0x1E 2 POT (Sub-Index 1 channel 1, Sub-Index 2 channel 2) Lo switch AI Filter Type defines the type of filter to be applied to FV, AI Filter Constant defines the iteration index. For both entries, subindex 01 refers to module channel 1 and subindex 02 refers to module channel 2. Value 0 1 2 3 4 5 6* 7 8 Description No filter 1 Operation ValueN = ValueN-1 + Moving average Node ID Baud rate kbps 20 50 100 125 250 500 800 1000 Input - ValueN-1 Filter Constant N Hi Lo Valid ID Node switch switch 0 1 01h (address 1) 0 2 02h (address 2) 7 F 7Fh (address 127D) * Bus length m 2500 1000 500 500 250 100 50 25 Decimal digits 2 2 2 3 3 3 3 3 Index 61A0h – AI Filter Type Index 61A1h – AI Filter Constant Bit Rate and Node ID configuration Bit rate Sensor type 0x21 0x24 0x25 0x2A 0x2F 0x33 0x34 0x78 2 Repeating average Value = 1 InputN N N depends on Filter Constant Module specific parameters Index 2000h – Cold Junction Measure Temperature of the cold junction, measured on the module’s terminal block. Available through TPD04. Index 2005h – 50/60 Hertz Input Filter Filter against the Vac power line frequency Note: * Default value Index 3000h – Node Address Current Module Node ID - Read only access Index 3001h – Baudrate Current Module Bit rate - Read only access Procedure for Node ID and Bit Rate configuration Scaling input variables The HI and LO hexadecimal rotary swithches set the module’s Bit Rate and CAN Node ID. During the configuration, the module must be off line and the CAN bus must be physically disconnected. To configure the module, follow the procedure: 1 Turn the Power OFF 2 Set the HI switch to “F” 3 Select the desired Bit Rate value by setting the LO switch following the table (e.g. “8” for 1 Mbps) 4 Turn the Power ON 5 Shift the HI switch to “E” (all the module service LEDs should flash) 6 Turn the Power OFF. Now configure Node ID 7 Set the HI and LO switches to the desired valid Node ID following the table 8 Turn the Power ON. Alternatively, at step 7 set the value 00h. Then, at the next Power ON, the last valid stored value will be resumed as Node ID. Default values: Bit Rate = 500 kbps, Node ID = 127D Index 9120h – AI Input Scaling 1FV Index 9121h – AI Input Scaling 1PV Index 9122h – AI Input Scaling 2FV Index 9123h – AI Input Scaling 2PV Index 9124h – AI Input Offset As regards linear inputs, the above variables allow the scale of the physical input to be changed and the desired physical unit to be assigned to this input. In addition, an offset can be added. PV Offset PV2 Span Measure PV1 FV1 1 2 Negative overload FV2 FV 3 4 Positive overload Index 9148h – AI Span start Index 9149h – AI Span end Parameter configuration Index 6110h - AI Sensor type Index 6131h - AI Physical Unit PV Index 6132h - AI Decimal Digits PV These two variables take into account the validity of the span values, indicating possible overloads and limiting the measure in correspondence of the extreme points of the span. The AI Physical Unit PV assigns SI units and prefixes to the process value, with the following structure: Span programmed values (°C) 31 MSB 24 23 Prefix 16 15 SI Numerator 8 7 SI Denominator 0 Reserved LSB Physical units and prefixes are coded according to CiA standard [3]. Within the DS404 profile, some additional physical units are specified: Code 55h 56h A1h A2h Physical unit m/s Nm at mmH2O Code A3h A4h ABh ACh Physical unit mmHg atm PSI °F Input TCJ TCK TCL TCN TCR TCS TCT Span Start -210°C -200°C -200°C 0°C 0°C 0°C -200°C Span End 1200°C 1372°C 600°C 1300°C 1600°C 1760°C 400°C Input LO Range PT100 PT1000 0...10V 0 0...150mV 0 4...20mA 0 0...20mA 0 POT 0 HI Range 10.5 155 21 21 100 Span Start -200°C -200°C 0V 0mV 4mA 0mA 0% Span End 600°C 600°C 10V 150mV 20mA 20mA 100%