Hardware Set-up
Value
Hexadecimal rotary switches, service and I/O LEDs
LED
Status
ON
RUN Blinking
Single flash
OFF
ON
Single flash
ERR Double flash
Triple flash
OFF
ON
ST Blinking
Single flash
OFF
PWR ON
OFF
Top view
•
Hi
ide
nt s
Fro
•
Lo
Negative
screwdriver
0.4 x 2.5 mm
•
•
Meaning
Operational
Pre-operational (CANopen)
STOPPED
Device in RESET state
BUS OFF
Warning limit reached
Error Control Event
Sync Error (CANopen)
No error. Device working
DIAG Error
INIT and DIAG running
Baud rate setting
Module OK and ready
Module Power Supply ON
Module Power Supply OFF
Sensor Decimal
Value
type
digits
TCJ (default) 0x01
2
PT1000
TCK
0x02
2
PT100 2w
TCL
0x03
2
PT100 4w
TCN
0x04
2
0...10V
TCR
0x05
2
0...150mV
TCS
0x06
2
4...20mA
TCT
0x07
2
0...20mA
PT100 3w 0x1E
2
POT
(Sub-Index 1 channel 1, Sub-Index 2 channel 2)
Lo switch
AI Filter Type defines the type of filter to be applied to FV, AI Filter Constant defines
the iteration index. For both entries, subindex 01 refers to module channel 1 and
subindex 02 refers to module channel 2.
Value
0
1
2
3
4
5
6*
7
8
Description
No filter
1
Operation
ValueN = ValueN-1 +
Moving average
Node ID
Baud rate
kbps
20
50
100
125
250
500
800
1000
Input - ValueN-1
Filter Constant
N
Hi
Lo
Valid ID Node
switch switch
0
1
01h (address 1)
0
2
02h (address 2)
7
F
7Fh (address 127D) *
Bus length
m
2500
1000
500
500
250
100
50
25
Decimal
digits
2
2
2
3
3
3
3
3
Index 61A0h – AI Filter Type
Index 61A1h – AI Filter Constant
Bit Rate and Node ID configuration
Bit rate
Sensor
type
0x21
0x24
0x25
0x2A
0x2F
0x33
0x34
0x78
2
Repeating average Value =
1
InputN
N
N depends on Filter Constant
Module specific parameters
Index 2000h – Cold Junction Measure
Temperature of the cold junction, measured on the module’s terminal block.
Available through TPD04.
Index 2005h – 50/60 Hertz Input Filter
Filter against the Vac power line frequency
Note: * Default value
Index 3000h – Node Address
Current Module Node ID - Read only access
Index 3001h – Baudrate
Current Module Bit rate - Read only access
Procedure for Node ID and Bit Rate configuration
Scaling input variables
The HI and LO hexadecimal rotary swithches set the module’s Bit Rate and CAN Node ID.
During the configuration, the module must be off line and the CAN bus must be physically
disconnected.
To configure the module, follow the procedure:
1 Turn the Power OFF
2 Set the HI switch to “F”
3 Select the desired Bit Rate value by setting the LO switch following the table
(e.g. “8” for 1 Mbps)
4 Turn the Power ON
5 Shift the HI switch to “E” (all the module service LEDs should flash)
6 Turn the Power OFF. Now configure Node ID
7 Set the HI and LO switches to the desired valid Node ID following the table
8 Turn the Power ON.
Alternatively, at step 7 set the value 00h. Then, at the next Power ON, the last valid stored
value will be resumed as Node ID.
Default values:
Bit Rate = 500 kbps, Node ID = 127D
Index 9120h – AI Input Scaling 1FV
Index 9121h – AI Input Scaling 1PV
Index 9122h – AI Input Scaling 2FV
Index 9123h – AI Input Scaling 2PV
Index 9124h – AI Input Offset
As regards linear inputs, the above variables allow the scale of the physical input
to be changed and the desired physical unit to be assigned to this input. In addition, an offset can be added.
PV
Offset
PV2
Span
Measure
PV1
FV1
1
2
Negative
overload
FV2 FV
3
4
Positive
overload
Index 9148h – AI Span start
Index 9149h – AI Span end
Parameter configuration
Index 6110h - AI Sensor type
Index 6131h - AI Physical Unit PV
Index 6132h - AI Decimal Digits PV
These two variables take into account the validity of the span values, indicating
possible overloads and limiting the measure in correspondence of the extreme
points of the span.
The AI Physical Unit PV assigns SI units and prefixes to the process value, with the following
structure:
Span programmed values (°C)
31
MSB
24 23
Prefix
16 15
SI Numerator
8 7
SI Denominator
0
Reserved
LSB
Physical units and prefixes are coded according to CiA standard [3]. Within the DS404
profile, some additional physical units are specified:
Code
55h
56h
A1h
A2h
Physical unit
m/s
Nm
at
mmH2O
Code
A3h
A4h
ABh
ACh
Physical unit
mmHg
atm
PSI
°F
Input
TCJ
TCK
TCL
TCN
TCR
TCS
TCT
Span
Start
-210°C
-200°C
-200°C
0°C
0°C
0°C
-200°C
Span
End
1200°C
1372°C
600°C
1300°C
1600°C
1760°C
400°C
Input
LO
Range
PT100
PT1000
0...10V
0
0...150mV 0
4...20mA 0
0...20mA 0
POT
0
HI
Range
10.5
155
21
21
100
Span
Start
-200°C
-200°C
0V
0mV
4mA
0mA
0%
Span
End
600°C
600°C
10V
150mV
20mA
20mA
100%