Section 6 - System Programming
Question 31, L1 - Cancel Code ............................................................................ Default = B
A cancel code can be transmitted to the Central Station if, after violation of a controlled zone,
a user code is entered. If the zone is programmed for restore, then the restore code can be
transmitted when the loop status has returned to normal, when bell timeout and loop are
normal, or when a code is entered. Entry of A in this field indicates that cancel codes are not
transmitted. In formats requiring two digits, the user number functions as the second digit.
NOTE: The event code for PID transmission is 406.
Question 31, L2 - Reserved - NOT USED
Question 31, L3 & L4 - CS Test Code................................................................. Default = AA
In these locations, enter the desired Central Station code for transmission of the system TEST
code. The frequency and type of test is defined in Question 10, Location 3. Entry of AA indicates that the system TEST is not transmitted.
NOTE: The event code for PID transmission is 602.
QUESTION 32
CS CODES for BYPASS, RESTORE (FIRE & DAY TRBL.) .......................... DEFAULT = AEFA
There are 4 locations (L1-L4) in this question, as follows:
Question 32, L1 - Bypass Code ............................................................................ Default = A
This is the single-digit system BYPASS CODE reported to the Central Station if a zone is bypassed upon arming. Entry of A means that bypasses are not transmitted. If a two-digit dialing format has been selected, then the Bypass code will be followed by the programmed second
digit of the zone's code.
Question 32, L2 - Restore Code ........................................................................... Default = E
This is the single-digit system RESTORE CODE reported to the Central Station. Restores will
be reported for burglary or 24-hour zones that have been programmed with the restore option.
Entry of A means that restores are not transmitted. If a two-digit dialer format has been pr ogrammed, then the restore code will be followed by the programmed second digit of the zone
code.
Question 32, L3 - Fire Trouble Code ..................................................................... Default = F
This is the single-digit system FIRE TROUBLE CODE reported to the Central Station. If a
two-digit format has been programmed, then this code will be followed by the second digit of
the respective zone's code. Entry of A indicates that troubles are not transmitted. If PID format is used, a dedicated event code of 373 will be transmitted.
Question 32, L4 - Day Trouble Code ..................................................................... Default = A
This is the single-digit system DAY TROUBLE CODE reported to the Central Station. If a
two-digit format has been programmed, then this code will be followed by the second digit of
the respective zone's code. Entry of A indicates that troubles are not transmitted. If PID format is used, a dedicated PID code of 156 will be transmitted.
If a zone is selected as a Fire Zone Type, the Fire Trouble CS Code (Question 32, Location 3)
must be enabled along with the Restore CS Code (Question 32, Location 2).
QUESTION 33
CS CODES for KEYPAD FIRE and KEYPAD AUXILIARY.............................. DEFAULT AAAA
There are 4 locations (L1-L4) in this question, as follows:
Question 33, L1 & L2 - Keypad Fire CS Code .................................................... Default = AA
L1 and L2 enables the KEYPAD FIRE condition code, which will be transmitted upon activation (by pressing the 7 and 9 keys on the keypad at the same time). This code can vary among
any of the zones pr ogrammed as fire.
NOTE: To disable the keypad fire condition and prevent CS reporting, enter AA. The keypad
fire condition is always audible.
Question 33, L3 & L4 - Keypad Auxiliary CS Code ............................................ Default = AA
6–27