ES100@ Digital Controller Protocol
Appendix K
Read PV Data (Sequence No. 254 (Hex 00FE))
Reads the PV data for the variable type “analog data” in the variable area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
+0
Number of send data words
+1
Number of units
+2
(Undefined)
Unit No.
+3
(Undefined)
Unit No.
~
+33
1st unit
2nd unit
~
(Undefined)
Offset
Unit No.
32nd unit (max.)
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
Number of units + 2
+1
Number of units (4 digits Hex)
0001 to 0020 (1 to 32 decimal)
+2
1st unit
Unit No. (2 digits BCD)
00 to 31
+3
2nd unit
Unit No. (2 digits BCD)
00 to 31
•
•
•
+33
(max.)
32nd unit
Unit No. (2 digits BCD)
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
+0
+1
Number of receive data words
+2
PV data (leftmost 4 digits)
+3
PV data (rightmost 4 digits)
+4
PV data (leftmost 4 digits)
PV data (rightmost 4 digits)
~
1st unit
2nd unit
~
+63
PV data (rightmost 4 digits)
+64
PV data (leftmost 4 digits)
Offset
Contents (data format)
32nd unit
Data
+0
Number of receive data words
(4 digits Hex)
Number of units × 2 + 1
+1
1st unit
PV data (rightmost 4 digits)
(4 digits BCD)
00000000 to 09999000
F indicates a negative number.
+2
1st unit
PV data (leftmost 4 digits)
(4 digits BCD)
+3
2nd unit
PV data (rightmost 4 digits)
(4 digits BCD)
+4
2nd unit
PV data (leftmost 4 digits)
(4 digits BCD)
00000000 to 09999000
F indicates a negative number.
•
•
•
+63
32nd unit
PV data (rightmost 4 digits)
(4 digits BCD)
+64
32nd unit
PV data (leftmost 4 digits)
(4 digits BCD)
00000000 to 09999000
F indicates a negative number.
567