Download FA1660C
Transcript
S E C T I O N 3 Installing the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring the control panel and all the peripheral devices. UL All devices are to be installed in accordance with UL 681, Standard for Installation and Classification of Burglar and Holdup Alarm Systems. In addition, since the transmission method utilizes DACT communication, UL 827, Standard for Central-Station Alarm Services should be referenced. Mounting the Control Cabinet To mount the control cabinet, perform the following steps: Step Action 1 Before mounting the circuit board, remove the metal knockouts for the wiring entry that you will be using. DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN INSTALLED. 2 Using fasteners or anchors (not supplied), mount the control cabinet to a sturdy wall in a clean, dry area that is not readily accessible to the general public. The back of the cabinet has 4 holes for this purpose. UL To provide certificated burglary service for UL installations, refer to the special requirements and Figure 3-2 Cabinet Attack Resistance Considerations to follow. For UL Commercial Burglary installations that require ATTACK RESISTANCE, use the cabinet included in the VISTA-ULKT kit. Installing the Cabinet Lock 1. 2. Remove cabinet door, then remove the lock knockout from the door. Insert the key into the lock. Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed. 3. When correctly positioned, push the lock until it is held securely by its snap tabs. Use an ADEMCO No. K4445 Lock (supplied). CHECK POSITION CABINET DOOR BOTTOM SNAP TAB STEP 1 STEP 2 cab_lock_snap-001-V0 UNLOCKED ADEMCO PUSH ADEMCO LOCKED PUSH ON LOCK UNTIL IT IS SEATED SECURELY SNAP TAB Figure 3-1: Installing the Lock Mercantile Premises Listing Guidelines • • • The panel door must be supervised. Mount the clip-on tamper switch (supplied) to the cabinet's right side wall as shown in the diagram below, and wire it to one of the hardwire zones. Use a bell with a tamper-protected housing such as the ADEMCO AB12M. The bell housing's tamper switch and inner tamper linings must also be wired to the hardwire zone. Assign the tampers’ hardwire zone to a burglary partition. Program the hardwire zone for day trouble/night alarm (zone type 5) when only one burglary partition is used. Program it for 24-hr. audible alarm (zone type 7) when more than one burglary partition is used. 3-1