5 Calculation formulas
5 Calculation formulas
5.1
One-phase network
One-phase network
Name
Parameter
Designation
Unit
Method of calculation
𝑀
Voltage (True RMS)
UA
V
π‘ˆπ΄ = √
1
βˆ‘ π‘ˆπ‘–2
𝑀
𝑖=1
where Ui is a subsequent sample of voltage UA-N
M = 2048 for 50Hz and 60 Hz
𝑀
π‘ˆπ΄π·πΆ =
Voltage DC component
Frequency
UADC
F
V
Hz
1
βˆ‘ π‘ˆπ‘–
𝑀
𝑖=1
where Ui is a subsequent sample of voltage UA-N
M = 2048 for 50Hz and 60 Hz
number of full voltage periods UA-N
counted during 10-sec period (clock time) divided by the
total duration of full periods
𝑀
Current (True RMS)
IA
A
𝐼𝐴 = √
1
βˆ‘ 𝐼𝑖2
𝑀
𝑖=1
where Ii is subsequent sample of current IA
M = 2048 for 50Hz and 60 Hz
𝑀
Current constant component
𝐼𝐴𝐷𝐢 =
IADC
A
1
βˆ‘ 𝐼𝑖
𝑀
𝑖=1
where Ii is a subsequent sample of current IA
M = 2048 for 50Hz and 60 Hz
𝑀
𝑃=
Active power
P
W
1
βˆ‘ π‘ˆπ‘– 𝐼𝑖
𝑀
𝑖=1
where Ui is a subsequent sample of voltage UA-N
Ii is a subsequent sample of current IA
M = 2048 for 50Hz and 60 Hz
40
𝑄𝐡 = βˆ‘ π‘ˆβ„Ž πΌβ„Ž sin πœ‘β„Ž
Budeanu reactive power
QB
var
Reactive power of fundamental component
Q1
var
β„Ž=1
where Uh is h-th harmonic of voltage UA-N
Ih jest h-th harmonic of current IA
οͺh is h-th angle between harmonic Uh and Ih
𝑄1 = π‘ˆ1𝐼1 sin πœ‘1
where U1 is fundamental component of voltage UA-N
I1 is fundamental component of current IA
οͺ1 is angle between fundamental components U1 and I1
Apparent power
S
VA
𝑆 = π‘ˆπ΄π‘…π‘€π‘† 𝐼𝐴𝑅𝑀𝑆
Apparent distortion
power
SN
VA
𝑆𝑁 = βˆšπ‘† 2 βˆ’ (π‘ˆ1 𝐼1)2
Budeanu distortion power
DB
var
𝐷𝐡 = βˆšπ‘† 2 βˆ’ 𝑃2 βˆ’ 𝑄𝐡2
Power Factor
PF
-
𝑃
𝑆
If PF < 0, then the load is of a generator type
If PF > 0, then the load is of a receiver type
𝑃𝐹 =
30