3 feet access at rear for all cabinets
1 foot, at left
and right sides
(for access only)
Server
cabinet
Exp
cabinet
Exp
cabinet
Exp
cabinet
NOTE: During operation, server and expansion
cabinets can be side by side—with 0
clearance— since there are no side clearance
requirements.
4 feet access at front for all cabinets
FIGURE 2-1
Server and Expansion Cabinet Access Areas—Top View
Planning the Electrical, Power, and Heat
Environment
Database Platform 420/3 Hardware
Database Platform 420/3 hardware should have two dedicated AC breaker panels.
The cabinet should not share these breaker panels with other, unrelated equipment. The
system requires two L30-R receptacles for the server cabinet, split between two
isolated circuits. For international installations, the system requires two Blue 32A
IEC309 (International) receptacles.
TABLE 2-1 lists the combined power requirement and heat dissipation of the server
cabinet in Database Platform 420/3.
TABLE 2-1
10
Power and Heat Requirements for Database Platform 420/3
Maximum Power Draw
Heat Dissipation
1060 W
3620 BTUs/hr