Page 20 of 98
Report No. 13603119 001
IEC / EN 60335-2-40
Clause
15
15.1
15.1.2
15.2
15.1.1
Requirement – Test
Result
Verdict
In case of flashover of functional insulation, the
appliance complies with clause 19 with the
clearance short circuited
N/A
MOISTURE RESISTANCE
——
(IEC) Enclosure provides the degree of moisture
protection against the ingress of water (rain,
overflow from the drain pan or defrosting, tests
of 15.2, 15.3, 11.6 and Cl. 16)
(IEC/EN 60335-2-40)
IPX4 (outdoor unit)
P
(IEC) Motor-compressor not operated and
detachable parts are removed during 15.2 and
15.3
(IEC
60335-2-40/A2)
P
(EN) Enclosure provides the degree of moisture
protection against the ingress of water (rain,
overflow from the drain pan or defrosting, tests
of 15.1.1, 15.1.2, 15.2, 11.6 and Cl. 16)
(EN 60335-2-40)
P
(EN) After test, water inside the enclosure has not
reduced the creepage distances and
clearances below the values of Cl. 29
(EN 60335-2-40)
P
(EN) Water valves containing live parts and that are
incorporated in external hoses for connection
of an appliance to the water mains are
subjected to the test specified for IPX7
appliances.
(IEC/EN 60335-1/A1)
N/A
(EN) Appliances normally fixed to a ceiling are
mounted underneath a horizontal unperforated
support that is constructed to prevent water
spraying onto its top surface. The pivot axis of
the oscillating tube is located at the same level
as the underside of the support and aligned
centrally with the appliance. The spray is
directed upwards.
(IEC/EN 60335-1/A1)
N/A
(EN) For IPX4 appliances, the movement of the
tube is limited to two times 90º from the
vertical for a period of 5 min.
(IEC/EN 60335-1/A1)
N/A
(IEC) Tests in accordance with IEC 60529 in
appliances other than IPX0, as specified
(EN)
(IEC/EN 60335-2-40)
Spillage of liquid does not affect the electrical
insulation
(EN 60335-2-40)
TRF No.: IECEN60335_2_40B
Outdoor unit
P
P