3--10
CPU Specifications and Operation
Setting the CPU
Network Address
The DL350 CPU has a built in DirectNET port. You can use the Handheld
Programmer to set the network address for the port and the port communication
parameters. The default settings are:
S Station Address 1
S Hex Mode
S Odd Parity
S 9600 Baud
The DirectNET Manual provides additional information about choosing the
communication settings for network operation.
Setting Retentive
Memory Ranges
The DL350 CPU provides certain ranges of retentive memory by default. The default
ranges are suitable for many applications, but you can change them if your
application requires additional retentive ranges or no retentive ranges at all. The
default settings are:
DL350
CPU Specifications
and Operation
Memory Area
Default Range
Avail. Range
Control Relays
C1000 -- C1777
C0 -- C1777
V--Memory
V1400 -- V37777
V0 -- V37777
Timers
None by default
T0 -- T377
Counters
CT0 -- CT177
CT0 -- CT177
Stages
None by default
S0 -- S1777
You can use AUX 57 to set the retentive ranges. You can also use DirectSOFT™
menus to select the retentive ranges.
WARNING: The DL350 CPU does not come with a battery. The super capacitor
will retain the values in the event of a power loss, but only for a short period of
time, depending on conditions. If the retentive ranges are important for your
application, make sure you obtain the optional battery.
Password
Protection
The DL350 CPU allows you to use a password to help minimize the risk of
unauthorized program and/or data changes. The DL350 offers multi--level
passwords for even more security. Once you enter a password you can “lock” the
CPU against access. Once the CPU is locked you must enter the password before
you can use a programming device to change any system parameters.
You can select an 8-digit numeric password. The CPUs are shipped from the factory
with a password of 00000000. All zeros removes the password protection. If a
password has been entered into the CPU you cannot enter all zeros to remove it.
Once you enter the correct password, you can change the password to all zeros to
remove the password protection.
For more information on passwords, see Appendix A, Auxiliary Functions, Aux 8* -Password Operations.
WARNING: Make sure you remember your password. If you forget your
password you will not be able to access the CPU. The CPU must be returned to
AutomationDirect to have the entire memory cleared in order to clear the
password which is the policy of the AutomationDirect.
DL350 User Manual, 2nd Edition