Configure I/O
1. Select “Motorprotect. reset” in the Function output 2&4 menu (15_6_1).
2. In the Tripped auto reset menu (14_6), select:
• "Yes" to enable automatic reset.
• "No" to disable automatic reset.
Extra Options When Motor Protection Reset is Not Used
Terminals 13–14 and 17–18 on the MIO 501 I/O board can be used as general outputs:
• Terminals 13–14 is referred to as Output 2.
• Terminals 17–18 is referred to as Output 4.
Function: General output
The General output is affected by selected conditions. When:
• At least one condition is true, the output is active.
• All conditions are false, the output is passive.
Conditions that can affect a General output
Condition
Description
Power failure
There is a mains power failure.
High level
Sump level is high.
High level float
High level float is active.
Low level
Sump level is low.
Low level float
Low level float is active.
Overflow
There is an overflow
P1 failure
Pump 1 is blocked by a pump failure.
P1 blocked
Pump 1 is blocked.
P2 failure
Pump 2 is blocked by a pump failure.
P2 blocked
Pump 2 is blocked.
Leakage P1
Leakage sensor for pump 1 is active.
Leakage P2
Leakage sensor for pump 2 is active.
No response P1
There is no response from pump 1.
No response P2
There is no response from pump 2.
Pump failures
The following pump failures can block a pump:
• High temperature
• Tripped motor protection
• Exceeded max run time (results in a temporary block)
Configure the General output
1. Select “General output” in the Function output 2&4 menu (15_6_1).
2. Specify conditions in the Output. 2 config menu (15_6_2).
Select:
• 1 to enable a condition.
• 0 to disable a condition.
3. Specify conditions in the Output. 4 config menu (15_6_3).