SD/SDHC card full
Display the maximal value
Display the minimal value
pulsating
permanent
Fig.6 Data switching scheme displayed on display lower line.
27,532
0,0000
27,532
27,532
05-07-11
27,532
18:23:35
27,532
%
0923-611-194
2
-55...185 oC
-50...180 oC
Cu100
Voltage mV
-65...185 oC
-60...180 oC
Ni1000-LG
-80...80 mV
-210...210 mV
-75...75 mV
-200...200 mV
-6...21 mV
-65...185 oC
-60...180 oC
Ni100-LG
-5...20 mV
-65...155 oC
-60...150 oC
Ni1000
-205...255 oC
-200...250 oC
-65...185 oC
-205...855 oC
-200...850 oC
-205...855 oC
-205...185 oC
-200...180 oC
-60...180 oC
-205...855 oC
-200...850 oC
-205...605 oC
-200...850 oC
Ni100
Pt1000
Pt500
Pt250
-200...600 oC
Resistance 5500 W
0...2050 W
0...5550 W
0...2000 W
Resistance 2000 W
0...420 W
-24...24 mA
-205...855 oC
0...400 W
Resistance 400 W
0...5500 W
-20...20 mA
Current
-28...28 V
-12...12 V
Maximal
measuring
range
2 GB
1 GB
4
4
1
1
2
1
2
1
2
4
3
3
3
4
5
2
2
4
10
10
5
Coefficant k
Table 2
Capacity
-200...850 oC
-24...24 V
Pt100
-10...10 V
Nominal
measuring
range
Voltage 24V
Input type
Voltage 10V
Inputs:
10. TECHNICAL DATA
0923-611-193
1
Order code
0.1
Accuracy
class
Table 3
As additional accessory to the transducers with SD/SDHC memory card
option (version P30U-X1XXXXXX) can be ordered the industrial SD card
with the capacity adapted to the user needs, according to the table below.
RS-485 monitoring mode provides
possibility of monitoring the frames
sent between Master and Slave in
RS-485 network. Value of any register read by Master from Slave can
be displayed on transducer’s screen. In this mode there is no possibility of reading by Master device
any data from the transducer.
1
1
2
2
1
1
1
2
2
1
2
1
0.5
0.1
0.5
0.1
0.5
0.1
Table 3
backlighted LCD, 2 x 8 signs
35 mm rail acc. to EN 60715
300 V for supply circuit and 50 V for
other circuit
<2000 m
basic,
III,
2,
Remark: Detailed technical data available in the service manual
· altitude above sea level
Safety Requirements:
acc. to EN61010-1
· isolation between circuits:
· installation category
· pollution level
· maximal phase-to-hearth
voltage:
Reference and rated operating conditions
- supply voltage
85...253 V d.c./a.c.(40...400 Hz)
or 20...40 V a.c.(40...400 Hz), 20...60 V d.c.,
- ambient temperature
-25...23...+55 oC
- storage temperature
-30...+70 oC
- relative humidity
25...95 % (condensation inadmissible)
- working position
any
Readout field:
Fixing way:
Overall dimensions: 120 x 45 x 100 mm
Power consumption: < 5 VA
- processing time < 200 ms
- relay - 1 or 2 relays; NO voltageless contacts - maximal load 5A 30V d.c.,
250V a.c.
- digital – RS-485 interface (Modbus RTU)
- class of analog output 0.1;
Outputs:
- analog, programmable, galvanically isolated current (0/4...20 mA, load
resistance £ 500 W) or voltage (0...10 V, load resistance ³ 500 W),
Monitor RS485
Master RS485
In the Master RS-485 mode the
transducer can read out one device with implemented Modbus protocol with RS-485 interface. In this
mode there is no possibility to connect master device to transducer.
390...1820 oC
400...1800 oC
Thermocouple B
-55...1765 oC
0...1760 oC
o
-210...1010 C
-50...280 oC
o
-200...1000 C
-240...1350 C
-40...260 oC
o
o
-200...1300 C
-50...450 C
-20...420 C
SD/SDHC card mounted and ready to work
9. ACCESSORIES
-55...1775 oC
0...1760 oC
SD/SDHC card mounted and ready to be
removed
Karta SD/SDHC card protected against
record
permanent
pulsating
pulsating
-280...1382 oC
-200...1370 oC
o
-20...420 oC
0...400 oC
o
-220...1210 oC
-200...1200 oC
-210...410 oC
Thermocouple R
Thermocouple E
Thermocouple N
Thermocouple S
Thermocouple K
Thermocouple J
-20...420 oC
0...400 oC
-200...400 oC
permanent
The P30 tranducers are standard equipped with internal memory
designed to storage the data, registered by transducer. Downloading
of archival data from internal memory can be done using memory
card SD/SDHC (option) or by using RS485 interface. For the transducers with SD/SDHC memory card option there is possibility of fast
rewriting the archive to the SD/SDHC card after pressing the buttons
and
.
combination:
8. ARCHIVING
Thermocouple T
Meaning
Display
method
Display lower line in the P30U transducer is multifunctional. After pressing
or
, the lower line functions are periodically switthe button
ched: unit, time, date, bargraph indicating the percent value of analog
output, the value of any register in the transducer.
Symbol
Table 1
P30U transducer is equipped with backlighted LCD display, consisted
of two lines, 8 signs each. The top row is used to display measured value (floating point format, 5 digits) and symbol of SD/SDHC card status.
After pressing button
or
symbol and value of maximal or minimal value will be displayed.
7. DISPLAY FORMAT
1
2
00
XX
P
E
X XX X
0
1
X
X
NOTES
Code P30U-111100E0 means transducer execu!on with current output, slot for
SD/SDHC card, with 2 alarm relays, 85..253 V a.c. / d.c. (40...400 Hz) power supply,
standard version, English language, without extra requirements.
Order example:
* a#er agreeing with the manufacturer
P30U - X XX X
Analog output:
current (0/4...20 mA)
1
voltage (0...10 V)
2
SD/SDHC card:
without slot for SD/SDHC card
0
with slot for SD/SDHC card
1
Addi!onal output:
NO relay, 5 A 30 V d.c., 250 V a.c.
1
supply 24 V d.c. / 30 mA
2
Supply:
85...253 V a.c./d.c.
20...40 V a.c., 20...60 V d.c.
Version:
standard
custom-made*
Language:
Polish
English
Acceptance tests:
without extra requirements
with an extra quality inspec!on cer!ficate
according to customer’s request*
11. ORDERING CODES
P30U-09/2