Chapter 6 EM9 series variable…
Figure 6-9 2-wire control mode1
1: 2-wire control mode 2 START/STOP command is determined by FWD terminal. Run direction is determined
by REV terminal.
Figure 6-9 2-wire control mode 2.
2: 3-wire control mode 1 Terminal Xin is the enable terminal in this control mode. START/STOP command is
determined by FWD terminal. Run direction is determined by REV terminal. Xin terminal is normally-closed input.
Figure 6-10 3-wire control mode 1.
K: Run direction button SB1: Start button SB2: Stop button Terminal Xin is the multi-functional input terminal of
X1~X4. The terminal function should be set to be 3 (3-wire control).
3: 3-wire control mode 2 Terminal Xin is the enable terminal in this control mode. START command is
determined by SB1 or SB3 terminal. Run direction is determined by SB1 or SB3 terminal too. STOP command is
determined by normally-closed input terminal SB2.
Figure 6-11 3-wire control mode 2