Commissioning 3.5 Multiple Connections via Port 502 General Some CP modules are able to multiplex TCP connections. In doing so several Modbus clients can establish a connection via port 502. The CP acts as Modbus server. Here you can find information which CP and which firmware release support multiple connections via port 502: www.siemens.com/s7modbus Pre-requisits To use the functionality, the parameterization must be carried out as follows: CP is server port 502 as local port unspecified TCP connection in NETPRO passive connection establishment Please note that only 1 connection is parameterized in NETPRO irrespective of the number of clients which address the CP as server. Number of released Connections The CP is capable to keep up to 4 connections to different clients. Displaying the Status of the Connection The status of the connection is displayed even in NETPRO online as well as in special diagnosis of the CP. As only 1 connection is parameterized in NETPRO, the display shows the status of all TCP connections to the several clients. As long as no client has established a connection “Passive connection establishment in progress“ is displayed. As soon as one client has established a connection “established” is displayed. It is not possible to check how many clients have actually established a connection to the CP. Characteristics of the Error Handling The FB MB_REDSV and the CP respectively must terminate and reestablish the connection in certain error situations. This action is carried out by the FB MB_REDSV. Thereby all existing connections via port 502 are terminated. Tip for your User Program When several connections are established via port 502, it is not possible to identify the client which has sent the recent request. If the clients use different UNIT numbers, the verification of the same in the user program allows a determination. SIMATIC Modbus/TCP Redundant Communication via CP443-1 in H-Systems 2XV9450-1MB11; Manual edition 2.2 3-11