Operating Notes 2.6.2 Joystick Response Definition Tables Normally the joystick response is defined by loading a predefined response table using the JT command. The loaded response table will remain chosen even when the controller is reset. For special purposes, it is possible to generate a user-defined joystick response table. Commands for user-defined joystick tables (see Command Reference section for more details): SIn Sets Index pointer for joystick table. A new table value can then be written with the SJ command. SI? Report command asking for the current index value SJn Sets the table value at active index to n. Range of n : 0 to 1024 Value 1024 represents maximum velocity, 0=standstill. SJ? Report command asking for the current table entry. Typical Command Sequence: SI0 SJ0 SI1 SJ5 SI2 SJ10 SI3 SJ15 etc. 2.7 Limit Sensors During operation, limit sensors (switches) can be used to stop motion at the end of the allowable travel range. Each of the two switches will interrupt motion in a particular direction. If positioning equipment from PI is used, the limit switches or sensors are pre-wired for operation with compatible Mercury™ controllers. The Mercury™ controller can be configured to accept either an active-high or an active-low stop signal from the limit sensors (both must be the same). www.pi.ws Native Commands MS176E Release 1.0.1 Page 11