Download [1.7 APPLICATION FUNCT.] (FUn
Transcript
[1.8 FAULT MANAGEMENT] (FLt-) Cards pairing This function is used to detect whenever a card has been replaced or the software has been modified in any way. When a pairing password is entered, the parameters of the cards currently inserted are stored. On every subsequent power-up these parameters are verified and in the event of a discrepancy the drive locks in HCF fault mode. Before the drive can be restarted you must revert to the original situation or re-enter the pairing password. The following parameters are verified: • The type of card for: all cards. • The software version for: the two control cards, the VW3A3202 extension card, the Controller Inside card and the communication cards. • The serial number for: both control cards. Code PPIPPI Name/Description b Adjustment range Factory setting OFF to 9999 [OFF] (OFF) [CARDS PAIRING] M [Pairing password] The [OFF] (OFF) value signifies that the cards pairing function is inactive. The [ON] (On) value signifies that cards pairing is active and that an access code must be entered in order to start the drive in the event of a cards pairing fault. As soon as the code has been entered the drive is unlocked and the value changes to [ON] (On). - The PPI code is an unlock code known only to Schneider Electric Product Support. 212