Download 51938 TECSPEC

Transcript
Annexure–1 (INDENT NO. 51938)
Scope, Specifications, Terms & Conditions for Supply, Implementation and commissioning LAN at
Kaiga Site of NPCIL
Item No. 20: UTP Information Outlets
Sr.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
Minimum Specifications / Functionalities / Capabilities
Compliance
(Y/N), Details
PCB based, Unshielded Twisted Pair, Category 6, Copper
Telecommunication Outlet Connector (I/O Modular) conforming to
TIA /EIA 568-C.2 and ISO/IEC11801
Features & Technical Specifications:
Modular Jack : 750 Mating cycles
Wire terminal accessories : 200 termination cycles
Integrated bend-limiting strain-relief unit for cable entry
Support cable pair termination process on the jacks at 90 degree
angle.
Should have mechanism to maintain quality of the termination irrespective of the skill level of the termination staff
Housing: Polyphenylene oxide, 94V-0 rated.
110 Block : polycarbonate, 94V-0 rated
Jack Contacts : Beryllium copper, plated with 1.27 mm [.000050]
thick gold in localized area and 3.81 mm [.000150] minimum thick
tin-lead in solder area over 1.27 mm [.000050] minimum thick
nickel under plate
Wiring Blocks : Polycarbonate, 94V-0 rated
Approvals : (a) UL Listed / CSA Approved
Performance Characteristics to be provided with bid : Attenuation,
NEXT, PS NEXT, FEXT and Return Loss
Make of the offered product
Item No. 21 & 22: UTP Patch Panel
Sr.
1.
2.
3.
4.
5.
6.
7.
8.
Minimum Specifications / Functionalities / Capabilities
Modular Patch Panel – compatible with CAT 5e & CAT 6 having Rear
Cable Manager
- Panels should accommodate 12/24 CAT 5e/Cat6 jacks in 1U and
have a proper shallow angle to minimize interference with cabinet
doors.
- Should be Angular type and suit for Open & close Racks
- Should Supports Gigabit Ethernet up to 250MHz
- Should offer modular panels offer complete flexibility and high
port density
- Panel should have Expansive cable management and labeling
facilities
- Should support for both shielded and unshielded solution and
Fully interoperable and backwards compatible
- Supply of around 800 nos of CAT5e keystone jacks and 450 nos of
CAT6 keystone jacks for populating the UTP patch panels.
Page 21 of 32
Compliance
(Y/N), Details