7.7.NON
NON--PROGRAMMABLE
PROGRAMMABLEPARAMETERS
PARAMETERSOF
OFBLDC
BLDCCOMPRESSOR
COMPRESSORDRIVER
DRIVER
CODE
F-00
F-01
F-02
F-03
F-04
F-05
F-06
F-07
F-08
F-09
F-10
F-11
F-12
F-13
F-14
F-15
F-16
F-17
F-18
PARAMETER
DATA
For Compressor 4 Pole
For Compressor 6 Pole
30.00Hz or 60.00Hz
Minimum frequency
20.00Hz
(depend on compressor model)
Maximum frequency
Depend on Compressor model
Acceleration time 1 (start interval)
12.5 sec. (2 rps/sec.)
8.3 sec. (2 rps/sec.)
Acceleration time 2 (normal operation)
12.5 sec. (2 rps/sec.)
8.3 sec. (2 rps/sec.)
Deceleration time 1 (normal operation)
12.5 sec. (2 rps/sec.)
8.3 sec. (2 rps/sec.)
Deceleration time 2 (deceleration to stop) 12.5 sec. (2 rps/sec.)
8.3 sec. (2 rps/sec.)
Start frequency
0.50Hz
0.50Hz
30.00Hz or 60.00Hz
Stop frequency
20.00Hz
(depend on compressor model)
Thermal overload level
100 % of rated current
100 % of rated current
Current limit with frequency level
100 % of rated current
100 % of rated current
Band of current limit
4 % of rated current
4 % of rated current
Deceleration time when current limit active 12.5 sec. (2 rps/sec.)
8.3 sec. (2 rps/sec.)
Node address for MODBUS
1
1
Baud rate
1200 bits/sec.
1200 bits/sec.
Data format
8-N-1
8-N-1
Reply interval
10 ms.
10 ms.
Communication loss time out
5 sec.
5 sec.
Time out action for MODBUS
Deceleration to stop
Deceleration to stop
Switching frequency
4kHz
4kHz
Note :
• User can see compressor model in Table 1
• User can not change the above parameter by keypad or MODBUS communication
• If user want to change it, please contact A.P.Y.ENGINEERING Co., Ltd.
8.8.PROGRAMMABLE
PROGRAMMABLEPARAMETERS
PARAMETERSOF
OFBLDC
BLDCCOMPRESSOR
COMPRESSORDRIVER
DRIVER
CODE
P-03
P-04
PARAMETER
Hold frequency (Address #3)
Hold frequency time (Address #4)
DATA
60.00 ~ 360.00Hz.
0.0 ~ 6000.0 sec.
DEFAULT
60.00
0.0
Note: User can change the above parameter by MODBUS communication. (Address #3 and address #4)