Download User manual Profibus
Transcript
7.7 Diagnosis Standard diagnosis for Profibus DP is supported. Profibus diagnosis consists of 6 bytes with the following contents: Byte Bit 0 1 Description Diag. station does not exist (set by master) Diag.station not ready Slave not ready for data exchange 2 Diag.cfg_Fault Byte 1 Inconsistent configuration data 3 Diag.ext_diag Slave has external diagnosis data 4 Diag.not supported Requested function not supported by slave 5 Diag.invalid slave response (fixes slave to 0) 6 Diag.prm_fault wrong parameterization (ident number, etc.) 7 Diag.master_lock (set by master) Slave has been parameterized by other master 0 Diag.prm_req Slave must be re-parameterized 1 Diag.Stat_diag static diagnosis (byte diag- bits) 2 fixed to ‘1 3 Diag.WD_ON Byte 2 Response monitoring active 4 Diag.freeze_mode freeze command received 5 Sync_mode sync command received 6 reserved 7 Diag.deactivated (set by master) 0 reserved 1 reserved 2 reserved 3 reserved Byte 3 4 reserved 5 reserved 6 reserved 7 Diag.ext_overflow Byte 4 Diag.master_add Master address after parameterization (FF without parameterization) Byte 5 Ident number high byte Byte 6 Ident number low byte Table 16: Diagnosis bytes Stat_diag: The slave cannot provide valid data due to a condition in the application. As a result, the master requests only diagnosis data until this bit will be reset. The firmware does not support this bit (permanently on 0) Ext_diag: If this bit is set, then a diagnosis entry must be present in the user-specific diagnosis area. This bit is always 0 in the AG03/1, since no user-specific diagnosis data is supported. AG03/1 (PB) Date: 08.07.2015 Page 33 of 35 Art.No. 86674 Mod. status 251/15