Download Preface

Transcript
Ch a pte r III Ge n e ra l De sc r i p t i o n o f F u n c t i o n B l o c k s
33
Time Sequence Frame:
ON
CW input
OFF
ON
CCW input
OFF
counting 1
2
3
up
Nms
F =
2
1
down
1,000
N
Functional Description:
1. The counter is counting up when there is a signal at input CW (counter).
2. The counter is counting down when there is a signal at input CWW (counter).
3. Retentivity function and high-speed running function are optional.
Notes:
1. The counting frequency is related to filtering duration. If the default filtering duration is 50ms, please choose
high-speed running mode when input frequency exceeds 4HZ.
2. I4~I7 are high-speed inputs. Each high-speed input only can be connected with a function block of highspeed counting in a program.
3.3.3 Tow-phase Counter (2PCT)
Line diagram/
Symbol in APB
A
H
2PCT
P
Description
Input R
A signal at input R resets the internal count value to zero, and
the output (R takes priority over A and B).
A/B phase
input
Input signal for two differential phases (A phase and B phase)
increases or decreases by multiplication factors 1, 2 and 4.
Q Output
When count value is reached, the Output Q is enabled.
Output P
Outputs the running value of the block to the Register D.
Q
B
R
Pin
Time Sequence Frame:
1.Multiplication factor 1:
2.Multiplication factor 2: