SECTION FOUR – CONFIGURATION AND TUNING
250
4.3.6.1.5
SETTING/LISTING [SLA/SLM/LLA/LLM] MOTOR VELOCITY LIMITS
The SLA/SLM commands set the automatic/manual mode motor velocity limits.
Manual mode is intended to be a reduced power operating mode used for initial tuning
or other situations in which full power could present personnel or equipment hazards,
(refer to 4.3.5.1.3). Although it is possible to set manual velocity limits higher than
automatic velocity limits, this is not recommended because it defeats the safety
principle of manual mode being a reduced power mode.
Automatic/Manual Mode Velocity Limits Units:
Automatic Mode Velocity Limit Default Value:
Automatic Mode Velocity Limit Min. Value:
Automatic Mode Velocity Limit Max Value:
Manual Mode Velocity Limit Default Value:
Manual Mode Velocity Limit Min. Value:
Manual Mode Velocity Limit Max Value:
Revolutions Per Minute
Velocity Scale Factor (N)*10Vd.c. (Max RPM)
50
Depependent on Motor
10% * Automatic Mode Default Value
50
Dependent on Motor
Issue C command to permanently save changes made using SLA and SLM.
Example usage of SLA and SLM commands:
>
SLA
Automatic Mode
Velocity Limit
5.800E 3 [RPM]
? 4000 <CR>
> SLM
Manual Mode
Velocity Limit
5.800E 2 [RPM]
? 400 <CR>
>
The LLA/LLM commands list the automatic/manual mode motor velocity limits.
Example usage of LLA and LLM commands:
>
LLA<CR>
Automatic Mode
Velocity Limit
4.000E 3 [RPM]
>
LLM<CR>
Manual Mode
Velocity Limit
4.000E 2 [RPM]
>
MOOG
T164 SERIES USER’S MANUAL