SECTION TWO - INSTALLATION AND WIRING
22
Surge current tolerance and single phase protection should also be considered when
selecting a circuit breaker (supply disconnecting device). (Refer to Section 1.1.2 for
additional information regarding the AC input circuit breaker.)
WARNING
The handle of the circuit breaker must be installed in a manner to be
easily accessible. It shall be located between 0.6 meters and 1.9 meters
above the servicing level. a maximum height of 1.7 meters is
recommended.
2.3 POWER LINE FILTERING
An a.c. power input Line Filter is required to be installed by the user in the a.c. power
input supply lines to the mains Isolation Transformer. The following power input Line
Filter is recommended:
Type: B84143-A36-R, manufactured by Siemens, Germany. (Rated 36 A r.m.s.)
The following Line Filters have also been tested with the configurations of T150-901
Power Supply and T164 Series Drives referenced in Section 1.3 of this Users Manual
and it has been found that they do not adversely affect the EMC characteristics of
these configurations:
Type: FN351-36-33, manufactured by Schaffner, Switzerland. (Rated 36 A r.m.s.)
Type: FN258-42-07, manufactured by Schaffner, Switzerland. (Rated 42 A r.m.s.)
Care must be taken when installing the a.c. power input Line Filter to ensure that the
ability of the filter to function effectively is not degraded.
When installing the Line Filter, care must be taken to implement the following
measures:
q Install the Line Filter on an earthed metal panel. There must be continuous
earth continuity with good HF bonding between this panel and the panel on
which the T150-901 Power Supply and T164 Series Drives are mounted.
This must result in continuous earth continuity with good HF bonding
between the enclosure of the Line Filter and the enclosures of the T150-901
Power Supply and T164 Series Drives.
q Remove paint or other insulating materials and provide conductive corrosion
protection at the mounting points for the Line Filter. Secure the filter using
conductive bolts and conductive locking washers.
MOOG