Texas Tech University, Santosh Pappu, August 2012 CHAPTER 6 RESULTS FOR COMPARATIVE STUDY OF WIND TURBINES The analysis was carried out on MATLAB-Simulink simulation environment. Both the configurations were simulated for the same length of time to make the analysis comparable. The same base values were used for both the configurations. The configurations were simulated for various wind conditions and fault conditions to check parameters like reactive power consumption, voltage stability, and active power transmission. The various conditions for both wind farms are simulated and demonstrated below. The voltage values are displayed in pu system and reactive power and active power are displayed in MW and MVAR respectively. The measurements are recorded at the terminals of the wind farm and at the 25kV bus for both the wind farms. 6.1 Wind Speeds ranging from 3-6m/s Both the configurations have been simulated for wind speeds ranging from 3-6m/s as shown in Fig. 4.1. The step change causes a change in reactive power and active power. Fig.6.1 shows the reactive power consumed for both the topologies. The wind farm consisting of DFIG consumes reactive power from 40sec. This is because the DFIG transmits power at low wind speeds. As the wind speed steps up to 6m/s, the DFIG starts generating active power and hence consuming reactive power, while the wind farm consisting of FSIG does not consume any reactive power as it does not generate any active power at low wind speeds. The voltage on the 25kV bus is stable for both the configurations as consumption of reactive power consumption is very less for low wind speeds. Fig.6.2 shows the active power transmission to the grid of both wind farms for this particular wind profile. The first few seconds show the initial transients on both the configurations. The wind farm consisting of FSIG does not generate any power for both the wind speeds. The wind farm consisting of DFIG starts generating active power as the wind speed steps at 20sec. 48