Download CS/CJ Series Programmable Controllers
Transcript
Section 6-1 Cycle Time/High-speed Processing Note The built-in interrupt inputs and high-speed counter inputs on a CJ1M CPU Unit can be used to activate interrupt tasks. Refer to the CJ Series Built-in I/O Operation Manual for details. 6-1-6 I/O Refreshing Methods There are three ways that the CS/CJ-series CPU Units can refresh data with Basic I/O Units and Special I/O Units: Cyclic refreshing, immediate refreshing, and execution of IORF(097). 1. Cyclic Refreshing I/O refreshing is performed after all of the instructions in executable tasks have been executed. (The PLC Setup can be set to disable cyclic refreshing of individual Special I/O Units.) END Task END Task END Task I/O refreshing Actual I/O data 2. Immediate Refreshing When an address in the I/O Area is specified as an operand in the immediaterefreshing variation of an instruction, that operand data will be refreshed when the instruction is executed. Immediate-refreshing instructions can refresh data allocated to Basic I/O Units. Immediate refreshing is also possible for the built-in I/O on CJ1M CPU Units. Actual I/O data Immediate refreshing CIO 0001 CIO 0002 CIO 0003 CIO 0004 Note 1. When the instruction contains a bit operand, the entire word containing that bit will be refreshed. When the instruction contains a word operand, that word will be refreshed. 2. Input and source data will be refreshed just before execution of the instruction. Output and destination data will be refreshed just after execution of the instruction. 3. The execution times for immediate-refreshing variations are longer than the regular variations of instructions, so the cycle time will be longer. Refer to 10-5 Instruction Execution Times and Number of Steps in the Operation Manual for details. 240