Download Wiring

Transcript
Chapter 2: Specifications
C0-01DD2-D – 8 DC Input/6 Sourcing DC Output Micro PLC
Wiring Diagram
C0-01DD2-D
24VDC
C1
+
X1
X2
+
X3
X4
RUN
C2
ERR
X5
X6
PORT1
X7
TX1
X8
C0-01DD2-D Built-in I/O Specifications - Inputs
Inputs per Module
Operating Voltage Range
Input Voltage Range
Input Current
Maximum Input Current
+
PWR
+
Input Impedance
ON Voltage Level
RX1
V1
Y1
L
RX2
Y2
L
Y3
L
Y4
L
PORT2
RS-485
PORT3
V2
TX3
Y5
L
RX3
Y6
L
OFF Voltage Level
+
TX2
24VDC
+
Minimum ON Current
Maximum OFF Current
OFF to ON Response
CO
ON to OFF Response
NOTE: When using Standard CPUs, you
must use CLICK programming software
version V1.20 or later.
Status Indicators
Commons
8 (Sink/Source)
24 VDC
21.6 - 26.4 VDC
X1-2: Typ 5 mA @ 24 VDC
X3-8: Typ 4 mA @ 24 VDC
X1-2: 6.0 mA @ 26.4 VDC
X3-8: 5.0 mA @ 26.4 VDC
X1-2: 4.7 k⏲ @ 24 VDC
X3-8: 6.8 k⏲ @ 24 VDC
X1-2: > 19 VDC
X3-8: > 19 VDC
X1-2: < 4 VDC
X3-8: < 7 VDC
X1-2: 4.5 mA
X3-8: 3.5 mA
X1-2: 0.1 mA
X3-8: 0.5 mA
X1-2: Typ 5 μs Max 20 μs
X3-8: Typ 2 ms Max 10 ms
X1-2: Typ 5 μs Max 20 μs
X3-8: Typ 3 ms Max 10 ms
Logic Side (8 points, green LED)
2 (4 points/common) Isolated
General Specifications
Current Consumption at 24VDC
Terminal Block Replacement Part No.
Weight
140 mA
C0-16TB
5.0 oz (140 g)
Equivalent Input Circuit
C0-01DD2-D Temperature Derating Chart
Internal Module Circuitry
+
Optical Isolator
INPUT
X1-X4
Typical
Inputs
6
+
24 VDC
4
2
C1 COM
To X2-X4
commons
+
8
Points
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
0
Optical Isolator
INPUT
X5-X8
Typical
0
32
10
50
30
85
40
104
50 55 °C
122 131 °F
Surrounding Air Temperature (°C/°F)
+
2–38
20
68
24 VDC
C2 COM
To X6-X8
commons
CLICK PLC Hardware User Manual, 4th Ed. – C0-USER-M