Download User Manual
Transcript
User Manual – R2485 & System The following please find the right steps for inserters a rectifier into the magazine. Step (1): Using one hand holds the bottom of the rectifier and meanwhile pulling out the handle. Step (2): Plugging a rectifier into the magazine smoothly. Step (3): Pushing the rectifier to the end and please make sure the handle which sitsfl at within the rectifier front panel. Note !! If operating a rectifier when not inserted in the magazine, or not inserted into its proper magazine, it will only operate at reduced output power (40%) since it senses that there is no fan current (no fan connected). 3.8. MUIB - Mini User Interface Board Connections between the MCSU, the external transducers and other inputs are made using the connectors provided on the MUIB, and allow monitoring of a total of two battery currents. Terminals are provided for alarm relay contacts, battery and ambient temperature sensors, two battery current transducers, LVDS control and circuit breaker operation detection using the breaker auxiliary contacts for both the battery and load circuit breakers. A 10-way ribbon cable port is available for direct connection of the optional MMIB1 single phase AC monitor module. 3.8.1. MUIB Connections The table of Figure 3.3 give detailed information on the pin-outs of the various MUIB connectors. MUIB outline and detailed connection diagram is given in Figure 3.4 showing the location and labeling of the connectors on the MUIB. This information is necessary when making various external connections of sensors and control during the system installation. The table of Figure 3.5 give detailed MUIB connectors function. Allis Electric Co.,Ltd. page 12 of total 82 2002.02