Download - Power Logic
Transcript
LPCT Type Current Sensors Test Accessories Installation ACE917 Injection Adapter Function DE80065 The ACE917 adapter is used to test the protection chain with a standard injection box, when the Sepam™ relay is connected to LPCT sensors. It is inserted between the standard injection box and the LPCT test plug (either integrated in the Sepam CCA670/CCA671 interface connector, or transferred by means of the CCA613 accessory). 2.76 (70) in. (mm) The following are supplied with the ACE917 injection adapter: b Power supply cord b 9.8 ft (3 m) cord to connect the ACE917 to the LPCT test plug on CCA670/CCA671 or CCA613 10.24 (260) 6.69 (170) Characteristics Power Supply Protection by Time-Delayed Fuse 0.2 x 0.79 in (5 mm x 20 mm) 115/230 V AC 0.25 A Rating DE50564 CCA613 Remote Test Plug Function The CCA613 test plug, flush-mounted on the front of the cubicle, is equipped with a 9.8 ft (3 m) cord to transfer data from the test plug integrated in the CCA670/CCA671 interface connector on the rear panel of the Sepam relay. DE80117 DE80045 Dimensions in. (mm) in. (mm) Mounting lug Accessory Connection Principle 6 Cable 2.66 (67.5) 2.66 (67.5) 1.73 (44) HAZARD OF CUTS Trim the edges of the cut-out plates to remove any jagged edges. Failure to follow this instruction can cause serious injury. DE80047 Front View with Cover Lifted CAUTION 1.97 (50) 3.15 (80) Right Side View 0.51 (13) in. (mm) 2.72 (69) 1.81 (46) Cut-Out © 2007 Schneider Electric. All Rights Reserved. 63230-216-208C1 139