Download Chapter 3 - Using the TeleFlow 2
Transcript
Chapter 4 - TeleFlow 2-Run ACCOL (TF2RUN) Load LOCAL SEQUENCE NUMBER GLOBAL SEQUENCE NUMBER RUN 1 FLOW RATE RUN 2 FLOW RATE STATION FLOW RATE MSCFH MSCFH MSCFH Log Break When the Log Break option is enabled, an archive log-break will occur when the Orifice plate size or other flow-related constants are changed. Flow Control Flow control on either run is achieved using PID control; the PID on each run can operate in either Raise/Lower mode or Analog mode, but because there is only one analog output, only the primary run can use it; simultaneous Raise/Lower operation is allowed. Raise/lower Flow-rate control is achieved using the PID3TERM module in combination with a PDO module. The Flow Controller uses a FLOW SETPOINT signal and the calculated flow rate signal as inputs to the PID3TERM module, the output of which is fed to a PDO module to generate raise/lower pulses on the discrete outputs (Raise on DO#1, Lower on DO#2). If the PID is configured to operate in Analog mode the PID output is scaled, as necessary, and applied to the Analog output on the expanded board. If the analog output is not used for PID control it is set in proportion to the Station flow rate (sum of both runs). Default PID settings are: Gain Integral Derivative 1 1 repeat/min 0 mins Deadband Valve travel Pulse width Max rate 0 30 secs 1 sec 5000 mscf/hr Run 2 flow control Raise/Lower operation uses IOEXP outputs (Raise on DIO#3, Lower on DIO#4). TeleFlow™ 4-16 2-Run (TF2RUN) Load and Menus