Download Chapter 3 - Using the TeleFlow 2

Transcript
Chapter 3 - Using the TeleFlow 2-Run Menus (TF2RUN)
controller uses this value (default = 5000 MSCFH) to convert the actual flow
rate to percent for use by the PID controller; therefore, this value should be set
as closely as possible to the expected operating maximum. To change the Span
value, press the [Page Up] key to clear the display and then type the desired
value. Once this value has been typed, press the [Ins] key.
VALVE TRAVEL TIME
Valve Travel Time is the amount of time it takes a Control Valve to go from
being fully open to fully closed (or from fully closed to fully open). The default
value is 30 Seconds. To change the value of the Valve Travel Time, press the
PAGE UP [Page Up] key to clear the display and then type the desired value.
Once this value has been typed, press the [Ins] key.
PRESSURE OVERRIDE (SET ONE OR BOTH TO ENABLE OVERRIDE)
When the PID controller is active in flow-control mode, it will adjust a pressure
valve to maintain the established flow rate setpoint. Pressure override is used in
situations where full line pressure should not be applied to the downstream
equipment or in circumstances where too low of a pressure should not be
allowed.
A Maximum and Minimum pressure can be configured which set the PID
controller to switch to pressure control mode whenever the line pressure
attempts to go outside the defined limits. The pressure override mode becomes
active when either or both limits are set to a non-zero value.
PRESSURE TAP LOCATION
The Pressure Tap location is specified as either upstream (UPSTRM) or
downstream (DNSTRM) with respect to the control valve. The action of the
override controller depends on the configured Tap location. When the pressure
tap is configured as Downstream of the control valve, pressure will rise as the
valve opens to increase the flow rate. Increasing demand will cause the valve to
open more. Should conditions occur that cause the pressure to exceed the
maximum pressure limit, the override will take control and close the valve to
maintain the configured maximum pressure. Should the valve attempt to close
and reduce pressure below the configured maximum pressure, the override will
take control to maintain the minimum pressure. When the pressure tap is
configured as Upstream, the action is reversed, i.e., when the maximum
pressure is exceeded the valve will open to lower the pressure. When the
minimum pressure is exceeded the valve will be closed.
Users are cautioned to test the regular override controller actions to verify correct
valve movement for all expected conditions.
TeleFlow™
3-47
2-Run (TF2RUN) Load and Menus