The UPS ground (earth) conductor carries leakage current from the loads in addition to any
leakage current generated by the UPS. This UPS generates no more than 0.5 mA of current (U
model), or 1 mA of current (A & E model). To limit the total leakage current to 3.5 mA, the
load leakage must be limited to 3 mA on the U model and 2.5 mA on the A & E model. The
three-wire receptacle that you plug the UPS into must have a good (low-impedance) ground
(protective earth) connection to provide a safe path for leakage current.