Download PLX30 Series - absatraining.com
Transcript
PLX30 Series Ethernet and Serial Gateways EIP Protocol User Manual 4. Next add a New Module under the Generic EtherNet Bridge and add a CIP-Connection. Here the parameters for the I/O connection are specified. The input and output sizes need to match the input and output sizes configured in PCB. The Address field value represents the connection number in PCB. By default all of the connections have 248 Input words, 248 Output words, and 0 Configuration words. The Comm format should be set to Data type INT, and the Assembly instances should be "1" for input, "2" for output, and "4" for configuration. 5. A CIP Connection will need to be added and configured for each I/O connection. Configuring EIP Class 1 Connections in PCB There are four configurable parameters for each I/O connection in PCB. Parameter Value Range Description Input Data Address 0-3999 This parameter specifies the starting address within the gateway’s virtual database for input data transferred to the PLC Input Size 0-248 This parameter specifies the number of Integers being transferred to the PLC's input image (248 integers max) Output Data Address 0-3999 This parameter specifies the starting address within the gateway’s virtual database for output data transferred to the PLC Output Size 0-248 This parameter specifies the number of integers being transferred to the PLC's output image (248 integers max) ProSoft Technology, Inc. July 10, 2013 Page 57 of 200