Download Man Al2000_eng - FF
Transcript
Page 5 - 10 AL 2000 User Guide 06/05/00 5.2.4 DIF16 Fault Checking Digital Input Module ACT ERR The DIF16 is a digital input module with 16 fault checking inputs isolated as a group. The following LED indicators are located on the front edge of the module: ACT (green) ERR (red) 0-15 (yellow) F0-15 (red) Module in operation The operating system has discovered a fault in the module Inputs I0-I15 are ON Fault in inputs I0-I15 The DIF16 can detect short and open-circuit faults in the cable. The status of each input can be determined from the LED indicators and can be used in the PLC program. Status indication is as follows: DIF16 F0 F8 0 8 F0 F8 I0 I8 F1 F9 1 9 F1 F9 I1 I9 F2 F10 2 10 F2 F10 I2 I10 F3 F11 3 11 F3 F11 I3 I11 F4 F12 4 12 F4 F12 I4 I12 F5 F13 5 13 F5 F13 I5 I13 F6 F14 6 14 F6 F14 I6 I14 F7 F15 7 15 F7 F15 I7 I15 0 I0 1 2 I1 3 4 I2 5 Status 0-15 OFF (0) ON (1) OFF (0) ON (1) Fault F0-15 OFF (0) OFF (0) ON (1) ON (1) Condition Input OFF Input ON Open circuit Short circuit 6 I3 7 8 I4 9 10 I5 11 Connection diagram for a switch 12 I6 13 14 I7 15 16 I8 17 18 I9 19 20 logic 0 logic 1 0.13 - 1.4 mA 1.9 - 6.7 mA GND I10 21 22 I11 23 24 Connections for DIN19234 or NAMUR transducer I12 25 26 I13 27 28 I14 29 30 I15 31 U+ GND FF-Automation Oy U- +24 V IN