Main Functions of REG24 Other Function: Anti-reset windup (Ar) and Output Convergence Value (bAL) Overview The parameters and z and are masked at default setting. are used to suppress overshoot. (Anti-reset wind-up) is automatically set by Auto-tuning. z NOTE: The control routine may not operate properly if the parameter are not correctly defined. Output Convergence Value (bAL) MV is calculated by adding the offset ( from PV and SV. ) to MV’, the result of PID calculation, 100% PV SV bAL increase Operation value MV MV' + PID + 50% bAL bAL bAL decrease 0% Set value (SV) Proportional band MV' (PV) Anti-reset windup (Ar) The integral range is SV±Ar. When PV is out of range, the Integral action does not work. Integral action PV Don't work Ar Work SV Ar Don't work Time EIO0000001300 09/2012 67