8.1
Program example for reading the inverter status
The following program turns on Y00 of the output unit when station 1 inverter is running
X0
X0F
M0
X1002
X1 SW80.0
0
7
M0
Check the data link status of the station 1
Y30
Turn on the output unit (Y00)
Inverter running (RX02)
10
END
Remote input
One
station
RXF to RX0
RX1F to RX10
X100F
X1000
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
[Inverter status]
Inverter status
b0: During forward rotation
b1: Reverse running
b2: Running (RUN)∗1
b3: Up to frequency (SU)∗1
b4: Overload alarm (OL)∗1
b5: Instantaneous power failure (IPF)∗1
b6: Frequency detection (FU)∗1
b7: Fault (ABC1)∗1
b8: ─ (ABC2)∗1
b9: ─ (DO0)∗1
b10: ─ (DO1)∗1
b11: ─ (DO2)∗1

78
These signals are initial values. You can change output signals using Pr.190 to Pr.196, Pr.313 to Pr.315 (output terminal function
selection.)
PROGRAMMING EXAMPLES