Download FR-A8NC INSTRUCTION MANUAL
Transcript
8.1 Program example for reading the inverter status The following program turns on Y00 of the output unit when station 1 inverter is running X0 X0F M0 X1002 X1 SW80.0 0 7 M0 Check the data link status of the station 1 Y30 Turn on the output unit (Y00) Inverter running (RX02) 10 END Remote input One station RXF to RX0 RX1F to RX10 X100F X1000 b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 [Inverter status] Inverter status b0: During forward rotation b1: Reverse running b2: Running (RUN)∗1 b3: Up to frequency (SU)∗1 b4: Overload alarm (OL)∗1 b5: Instantaneous power failure (IPF)∗1 b6: Frequency detection (FU)∗1 b7: Fault (ABC1)∗1 b8: ─ (ABC2)∗1 b9: ─ (DO0)∗1 b10: ─ (DO1)∗1 b11: ─ (DO2)∗1 78 These signals are initial values. You can change output signals using Pr.190 to Pr.196, Pr.313 to Pr.315 (output terminal function selection.) PROGRAMMING EXAMPLES