Download ISM0122

Transcript
Ordering information
Model:
D5293S
Operating parameters are programmable from PC by the GM Pocket Portable Adapter
PPC5092 via USB serial line and SWC5090 Configurator software.
Power Bus and DIN-Rail accessories:
Connector JDFT050
Cover and fix MCHP196
Terminal block male MOR017
Terminal block female MOR022
Front Panel and Features
9
5
1
10
6
2
11
7
3
12
8
4
• SIL 3 according to IEC 61508 for Tproof = 10 / 20 yrs (10 / 20 % of total SIF).
• SIL 2 according to IEC 61508 for Tproof = 20 yrs (10 % of total SIF).
• PFDavg (1 year) 7.01 E-06, SFF 99.60 % for NE Load.
• Installation in Zone 2.
• Line input monitoring.
CONFIG
• Relay coil short circuit detection.
• Line and Load short/open circuit detection.
PWR
FLT
STS
• Solenoid resistance measurement even in presence of serial connected diodes
(proprietary patent pending resistance measuring technique).
• RMS measurement of voltage (before and after load energization) and current supplied to the load via relay contacts.
• Automatic acquisition of voltage, current and solenoid resistance values at start up.
• 4 A high availability SIL 3 contacts for NE load.
• 6 A inrush current at 24 Vdc / 250 Vac.
SIL 3
• Input/Output/Supply isolation.
D5293
• EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
13
14
15
16
• ATEX, IECEx, Russian and Ukrainian Certifications.
21
22
23
24
• Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without Power Bus, or customized Termination Boards.
Terminal block connections
4
3
2
1
8
7
6
5
13 14 15 16
21 22 23 24
12 11 10 9
SAFE AREA
13
(SIL 3) + Output Normally Energized Load
1
+ Input
14
(SIL 3) - Output Normally Energized Load
2
- Input
15
+ Load Power DC/AC
3
Fault Output 1 (30 V, 500 mA) or optional external testing resistor
16
- Load Power DC/AC
4
Fault Output 1 (30 V, 500 mA) or optional external testing resistor
21
Earth
5
A- Modbus Input/Output RS485
22
Not used
6
B+ Modbus Input/Output RS485
23
Not used
A- Modbus Input/Output RS485 (internally connected to terminal 5)
24
Not used
7
8
9
+ Power Supply 24 Vdc
10
- Power Supply 24 Vdc
11
12
Fault Output 2 (250 V, 3 A)
G.M. International ISM0122-3
B+ Modbus Input/Output RS485 (internally connected to terminal 6)
Fault Output 2 (250 V, 3 A)
D5293 - 4 A SIL 3 Relay Output Module for NE Load with open/short circuit diagnostic
3