Download 21219977A
Transcript
Polling Instrument DA Control ST HOST (IMR) Max. 100 ms Handshake not necessary Response Telegram MD113 Slave 100 ms ST max. 2300 ms 1500 ms 1200 ms Entire Polling Cycle 5s 12.4. Transfer Protocol Data transmission between the measurement point and the MSR takes place in accordance with a strict master-slave procedure. The measurement site itself never initiates contact with the MSR. The MSR transmits commands to the measurement site, which then responds with an answer block. All the commands contain an address, i.e. the measurement unit identifier. The addresses can be used to address either the entire measurement site or individual measurement units at the measurement site. Response blocks also contain from one to four measurement device identifiers for the purposes of identification and allocation. See section 12.6 for the definitions of the individual telegrams (message blocks). Data Protocol Structure: Byte 001: STX (Start of Text) Byte 002-nnn: <TEXT>; Message Text; max. 120 Characters; USASCII coded Byte nnn+1: ETX (End of Text) Byte nnn+2/3: BCC (Block Check Character) The response from the measurement site is always in the same format as that of the command it received. APM-2 45